Installing/mounting
4.2 Installation instructions
4.2.2.3

Installation in a drop line

Installation in a drop line
Installation in a drop line is only recommended if a pipeline reduction or orifice with a smaller
cross-section can be installed to create back-pressure and prevent the sensor from being
partially drained while measuring.
Figure 4-7
4.2.2.4
Mounting the sensor
● Install the sensor in well-supported pipelines in order to support the weight of the
flowmeter.
● Center the connecting pipelines axially in order to assure a stress-free installation. The
flowmeter must not be used to bring the rest of the pipework into line; make sure the
pipework is correctly aligned before inserting the flow sensor.
● Install two supports or hangers symmetrically and stress-free on the pipeline in close
proximity to the process connections.
Note
Handling
Never lift the flowmeter using the housing, that is always lift the sensor body.
58
Back pressure orifice
On / off valve
Installation in drop line
FC430 (From firmware 4.0)
Operating Instructions, 06/2017, A5E39789392-AA