Functions
8.6 Inputs and outputs
● Fail Safe Mode = Maximum current
● Low-Flow Cut-Off = 25 kg/h
Positive flow across zero with positive scaling
Current output setting
● Process value = Massflow
● Direction = Bidirectional
● Current Mode = 4-20 mA NAMUR
● Upper Scaling = 400 kg/h
● Lower Scaling = -100 kg/h
● Fail Safe Mode = Maximum current
● Low-Flow Cut-Off = 25 kg/h
162
mA
-100 kg/h
Lower scaling
Low-flow cut-off
Upper scaling
Maximum measurement value
Upper range
Lower range
Minimum measurement value
Lower alarm value
Measurement range
Kg/h
400 kg/h
FC430 (From firmware 4.0)
Operating Instructions, 06/2017, A5E39789392-AA