Siemens SITRANS FC430 Operating Instructions Manual page 349

Coriolis flowmeters
Hide thumbs Also See for SITRANS FC430:
Table of Contents

Advertisement

HMI menu ID
Parameter
2.4.2.6.2
Direction
2.4.2.6.3
Frequency value high
2.4.2.6.4
Frequency value low
2.4.2.6.5
Upper range value
2.4.2.6.6
Lower range value
2.4.2.6.7
Damping value
2.4.2.6.8
Fail-safe behavior
2.4.2.6.9
Fail-safe value
2.4.2.6.10
Fail-safe minimum dura‐
tion
2.4.2.7
Pulse output
2.4.2.7.1
Process value
2.4.2.7.2
Direction
FC430 (From firmware 4.0)
Operating Instructions, 06/2017, A5E39789392-AA
Description
Select measured flow direction.
The flow meter will only output
current when flow value is meas‐
ured in selected direction.
Assign maximum frequency val‐
ue
Assign minimum frequency val‐
ue
Assign process value to the
nominal upper range value
Assign process value to the
nominal lower range value
Set filter time constant. Defines
the damping of the current out‐
put signal.
Select current output reaction in
case of a fault.
Define fail-safe current output
value if 'Fail-safe behaviour' pa‐
rameter is set to 'Fail-safe value'.
Minimum time the output stays
in fail-safe mode. Short events
will be prolonged.
Select process value for current
output.
Select measured flow direction.
The flow meter will only output
current when flow value is meas‐
ured in selected direction.
E.5 Inputs and outputs
Default value
Value range
[unit]
Positive
● Positive
● Negative
● Bidirectional
● Bidirectional
(symmetric)
10000 Hz
● 0 to 12500 Hz
0 Hz
● 0 to 12500 Hz
1)
1)
1)
1)
0 s
● 0 to 100 s
Last valid value
● Minimum
frequency
● Maximum
frequency
● Last valid
value
● Current value
● Fail-safe
value
0 Hz
● 0 to 12500 Hz
0 s
● 0 to 100 s
Mass flow
● Mass flow
● Volume flow
● Standard
volume flow
● Fraction flow
Media A
● Fraction flow
Media B
Positive
● Positive
● Negative
● Bidirectional
Default settings
Access
level
User
User
User
User
User
User
User
User
User
User
User
349