Symbols
Table 10-1
Mapping of device states in SIMATIC products (e.g. SIMATIC PDM) and NE107
SIMATIC PDM / PLC
Icon
Device
Pri‐
status
ority
Mainte‐
1
nance
alarm
Mainte‐
2
nance de‐
manded
Mainte‐
3
nance re‐
quired
Manual
4
mode
Simula‐
5
tion mode
Out of
6
service
Configura‐
7
tion error
FC430 (From firmware 4.0)
Operating Instructions, 06/2017, A5E39789392-AA
NAMUR NE 107
Icon
Device
Pri‐
status
ority
Failure
1
Mainte‐
3
nance re‐
quired
Mainte‐
3
nance re‐
quired
Function
2
check
Function
2
check
Function
2
check
Failure
1
Description
Output signal invalid due to malfunc‐
tion in the field device or its peripher‐
als.
Output signal is still valid but wear re‐
serve is nearly exhausted, or a func‐
tion will soon be restricted.
Output signal is still valid. No func‐
tional restriction has been detected
but wear reserve is expected in the
next weeks.
Output signal temporarily invalid (e.g.
frozen) due to ongoing work on the
device.
Output signal temporarily does not
represent the process because out‐
put based on a simulation value.
Output signal does not represent
process value.
Device mode is set to "Out of service".
Output signal invalid due to a param‐
eter setting, an interconnection error
or a configuration error in HW.
Diagnosing and troubleshooting
10.1 Device status symbols
Measure
Maintenance is required
immediately.
Maintenance is strongly
recommended as soon as
possible.
Maintenance of device
should be planned.
Disable manual mode via
HMI or engineering sys‐
tem.
Disable simulation mode
via HMI or engineering
system or restart device.
Disable "Out of service"
and activate normal opera‐
tion mode.
Check device hardware
configuration or parameter
settings via HMI or engi‐
neering system.