DNP V3.00 Device Profile
3.3

Binary Input Points

Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Name
0
>79 ON
01
>79 OFF
02
> BLOCK 79
03
>79 T WAIT
04
>79 TRIP 1p
05
>79 TRIP 3p
06
>Enable ANSI#-2
07
>ZSC ON
08
>ZSC OFF
09
TRIP Gnd Fault
10
TRIP Ph Fault
11
ZSC active
12
ZSC ON
13
ZSC OFF
14
>CB Ready
15
79 OFF
16
79 ON
17
CB is NOT ready
18
79 DynBlock
19
79 in progress
20
79 Close
21
79 Successful
22
79 Lockout
23
79 L_N Sequence
24
79 L-L Sequence
25
>BLOCK 50-2
26
>BLOCK 50-1
27
3-6

Automatic reclosure status

>79 ON; Automatic reclosure ON; ON = 1, OFF = 0
>79 OFF; ON = 1, OFF = 0
>BLOCK 79; ON = 1, OFF = 0
>79-A/R coordination control; ON = 1, OFF = 0
>79 Ext. 1pole TRIP for internal A/R; ON = 1, OFF = 0
>79 Ext. 3pole TRIP for internal A/R; ON = 1, OFF = 0
>Enable 50/67-(N)-2 (override 79 blk); ON = 1, OFF = 0
>Switch zone sequence coordination ON; ON = 1, OFF = 0
>Switch zone sequence coordination OFF; ON = 1, OFF = 0
TRIP Ground Fault; ON = 1, OFF = 0
TRIP Phase Fault; ON = 1, OFF = 0
Zone Sequencing is active; ON = 1, OFF = 0
Zone sequence coordination switched ON; ON = 1, OFF = 0
Zone sequence coordination switched OFF; ON = 1, OFF = 0
>Circuit breaker READY for reclosing; ON = 1, OFF = 0
79 Auto recloser is switched OFF; ON = 1, OFF = 0
79 Auto recloser is switched ON; ON = 1, OFF = 0
Circuit breaker is NOT ready; ON = 1, OFF = 0
79 – Auto-reclose is dynamically BLOCKED; ON = 1, OFF = 0
79 – in progress; ON = 1, OFF = 0
79 – Close command; ON = 1
79 – cycle successful; ON = 1, OFF = 0
79 – Lockout; ON = 1, OFF = 0
79-A/R single phase reclosing sequence; Program earthfault
is running = 1, Program is deactivated = 0
79-A/R multi-phase reclosing sequence; ON = 1, OFF = 0

Time Overcurrent protection

>BLOCK 50-2; ON = 1, OFF = 0
>BLOCK 50-1; ON = 1, OFF = 0
>BLOCK 51; ON = 1, OFF = 0
Description
7SJ61/62/63 6MD63 DNP3.0 Device Profile Document
2701
3
2702
3
2703
3
2705
3
2715
3
2716
3
2720
3
2722
3
2723
3
2869
3
2870
3
2883
3
2884
3
2885
3
2730
3
2781
2
2782
2
2784
2
2785
3
2801
2
2851
3
2862
3
2863
1
2878
3
2879
3
1721
3
1722
3
1723
3
C53000-L1840-A001-01