YASKAWA E-7-Series SGD7S Product Manual page 226

Servo, analog voltage/pulse train references
Table of Contents

Advertisement

When Changing Input Signal Allocations (Pn50A = n.1)
The following four signals are assigned to CN1-40 to CN1-46 on the I/O signal connector: /C-
SEL (Control Selection), /SPD-A and /SPD-B (Internal Set Speed Selection) signals, and /SPD-
D (Motor Direction) signal.
The control method is switched by turning the /C-SEL signal ON and OFF.
Type
Signal Connector Pin No.
Input
/C-SEL Must be allocated.
Note: You must allocate the /C-SEL signal to use it. Use Pn50C = n.X (/C-SEL (Control Selection Input) Signal
Allocation) to allocate the signal to a connector pin. Refer to the following section for details.
6.1.2 Output Signal Allocations on page 6-6
The operating method for internal set speed control (i.e., the /C-SEL signal is OFF) is given
below.
• Rotary Servomotors
Input Signals
/SPD-D
/SPD-A
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
ON
• Linear Servomotors
Input Signals
/SPD-D
/SPD-A
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
ON
Note: You must allocate the /SPD-D, /SPD-A, and /SPD-B signals to use them. You can use the following parame-
ters to allocate the signal to a terminal.
• Pn50C = n.X (/SPD-D (Motor Direction) Signal Allocation)
• Pn50C = n.X (/SPD-A (Internal Set Speed Selection Input) Signal Allocation)
• Pn50C = n.X (/SPD-B (Internal Set Speed Selection Input) Signal Allocation)
Refer to the following section for details.
6.1.1 Input Signal Allocations on page 6-4
6.10.1 Setting Pn000 = n.X (Control Method Selection) to 4, 5, or 6
Control Method for Setting of Pn000 = n.X
Setting

n.
ON (closed)
Speed control
OFF (open)
Internal set speed control
Motor
Direction
/SPD-B
OFF
Stops the motor with an internal speed of 0.
Operates the motor with internal set speed 1,
ON
which is set in Pn301.
Forward
Operates the motor with internal set speed 2,
ON
which is set in Pn302.
Operates the motor with internal set speed 3,
OFF
which is set in Pn303.
OFF
Stops the motor with an internal speed of 0.
Operates the motor with internal set speed 1,
ON
which is set in Pn301.
Reverse
Operates the motor with internal set speed 2,
ON
which is set in Pn302.
Operates the motor with internal set speed 3,
OFF
which is set in Pn303.
Motor
Direction
/SPD-B
OFF
Stops the motor with an internal speed of 0.
Operates the motor with internal set speed 1,
ON
which is set in Pn380.
Forward
Operates the motor with internal set speed 2,
ON
which is set in Pn381.
Operates the motor with internal set speed 3,
OFF
which is set in Pn382.
OFF
Stops the motor with an internal speed of 0.
Operates the motor with internal set speed 1,
ON
which is set in Pn380.
Reverse
Operates the motor with internal set speed 2,
ON
which is set in Pn381.
Operates the motor with internal set speed 3,
OFF
which is set in Pn382.
6.10 Selecting Combined Control Methods

4
n.
5
Position control
Internal set speed control
Motor Speed
Motor Speed

n.
6
Torque control
Internal set speed control
6
6-57