YASKAWA E-7-Series SGD7S Product Manual page 513

Servo, analog voltage/pulse train references
Table of Contents

Advertisement

13.4 Utility Function (Fn) Operations on the Panel Operator
13.4.32 Easy FFT (Fn206)
Step
3
4
5
6
7
8
13-30
Panel Display after
Operation
MODE/SET
(Reference amplitude
setting)
MODE/SET
MODE/SET
(Ready to operate sta-
tus)
MODE/SET
(Flashing)
MODE/SET
Slight movement in
Servomotor
(Detection result dis-
play example)
Keys
Press the DATA/SHIFT Key for approximately one sec-
ond. The display shown on the left will appear and the
Panel Operator will enter Reference Amplitude Setting
DATA/
Mode.
Press the UP Key or DOWN Key to set the reference
amplitude. Reference amplitude setting range: 1 to 800
Note: 1. If you are setting Easy FFT for the first time, do not
change the reference amplitude setting, but rather
start from the default value of 15. Although increasing
the reference amplitude will increase the detection
DATA/
accuracy, the vibration and noise in the machine will
increase momentarily. Increase the reference ampli-
tude a little at a time and observe the results.
2. The set reference amplitude will be stored in Pn456.
Press the DATA/SHIFT Key for approximately one sec-
ond. The ready to operate status will be entered.
DATA/
Press the MODE/SET Key to turn ON the servo.
Additional Information
Press the MODE/SET Key again to turn OFF the servo.
DATA/
Return to step 5.
While the servo is ON, press the UP Key (forward) or
the DOWN Key (reverse). The Servomotor will auto-
matically perform round-trip operation, moving in for-
ward and reverse several times for 1/4th of a rotation
for a Rotary Servomotor and 10 mm or less for a Linear
Servomotor. The Servomotor performs this operation
for approximately 2 seconds. During this operation, the
display shown on the left will flash.
DATA/
Note: 1. Press the MODE/SET Key to cancel the operation.
Return to step 5.
2. The Servomotor will move slightly. Also at the same
time, the Servomotor will emit noise. To ensure
safety, do not approach or enter the range of
machine motion.
If detection is completed normally, E_FFt will stop
flashing and the detected resonance frequency will be
displayed. If detection fails, F---- will be displayed.
To check the results, go to step 9. To monitor the reso-
nance frequency without setting the detection result,
press the DATA/SHIFT Key for approximately one sec-
ond and return to step 2.
 IMPORTANT
If the operation ended normally but it took two sec-
onds or longer, the detection accuracy may not be suf-
ficient. Increase the reference amplitude to a value
higher than 15 to increase the detection accuracy.
Although increasing the reference amplitude will
increase the detection accuracy, the vibration and
noise in the machine will increase momentarily.
Increase the reference amplitude a little at a time and
observe the results.
Operation