J1000
compact v/f control drive
200 v class, three-phase input: 0.1 to 5.5 kw
200 v class, single-phase input: 0.1 to 2.2 kw
400 v class, three-phase input: 0.2 to 5.5 kw (265 pages)
Page 3
Quick Reference for Bypass Parameters Parameter Factory User Parameter Factory User Parameter Factory User Parameter Factory User Number Setting Setting Number Setting Setting Number Setting Setting Number Setting Setting A1-00 b5-04 L1-05 E1-05 208V, 230V or 460V A1-01 b5-06 L2-01 kVA Dep.
To avoid unnecessary fault displays caused by contactors or output switches placed between Drive and motor, auxiliary • contacts must be properly integrated into the control logic circuit. YASKAWA is not responsible for any modification of the product made by the user; doing so will void the warranty. This • product must not be modified.
Page 5
WARNING Some drawings in this manual may be shown with protective covers or shields removed, to describe details. These must be • replaced before operation. Observe electrostatic discharge procedures when handling circuit cards to prevent ESD damage. • The equipment may start unexpectedly upon application of power. Clear all personnel from the Drive, motor, and machine •...
Product Description The E7N Bypass unit provides a means of bypassing the Drive while allowing the motor to operate at full speed, directly from the AC line. It incorporates an AC Drive and two contactor Bypass arrangement in a single UL listed enclosure. The two electrically interlocked IEC rated contactors isolate the Drive from the load when operating in Bypass mode.
Page 7
This manual may describe trademarked equipment, which is the property of other companies. These trademarks are the property of the registered owner companies and may include the following: APOGEE FLN, trademark of Siemens Building Technologies, Inc. ® Metasys , trademark of Johnson Controls Inc. ®...
Table of Contents Quick Reference Parameter List ............Inside front cover Warnings and Cautions ....................i Introduction........................iii Chapter 1 - Physical Installation ................1-1 Bypass Model Number and Enclosure Style .............. 2 Enclosure Data ......................3 Confirmations upon Delivery ..................5 Bypass Product Options ..................... 7 Bypass Component Descriptions ................
Page 11
Chapter 6 - Diagnostics & Troubleshooting ............6-1 E7N Bypass PCB and H/O/A Control Panel Diagnostics ........... 2 Drive Diagnostics ....................... 6 Drive Troubleshooting ....................19 Drive Main Circuit Test Procedure ................25 Drive Date Stamp Information .................. 29 Chapter 7 - Maintenance .................... 7-1 E7N Maintenance .......................
Page 12
Chapter 1 Physical Installation This chapter describes the checks required upon receiving and the installation process for a Drive and Bypass unit. Bypass Model Number and Enclosure Style ........2 Enclosure Data ................3 Bypass Unit Enclosures ............. 4 Confirmations upon Delivery ............5 Receiving Checks ..............
Bypass Model Number and Enclosure Style The Bypass covers two voltage ranges: 208 VAC and 480 VAC. Ratings applicable are from 1/2 to 50 HP. Table 1.1 Bypass Bypass Bypass Base Model Number Continuous Uses Voltage Output Basic Drive Current Model-Number NEMA 1 (Amps)
The Bypass unit is thoroughly tested at the factory. Any damages or shortages evident when the equipment is received must be reported immediately to the commercial carrier that transported the material. Shipping damage is not covered by the Yaskawa warranty. After unpacking and inspecting for damage, verify that internal wire connections have not come loose during shipment by spot checking wire terminations with a screwdriver or the appropriate tool.
Page 17
Drive Nameplate Information A nameplate is also attached to the right side of the Drive inside the Bypass enclosure. The following nameplate is an example for a standard Drive. Drive Enclosure and Drive Model Number Revision Code Input Power Specifications Output Power Specifications Weight Serial Number...
Bypass Product Options Option B 3 Contactor bypass: Isolates the drive circuit by adding a separate drive input contactor (100 kA short circuit current rating is provided when using this option in conjunction with option D below). Option C Motor Circuit Protector (MCP)/Disconnect: Replaces the standard input disconnect switch and provides short circuit protection integral with the Drive and Bypass package.
Page 19
Option X 3% DC Bus Reactor: Attenuates harmonic distortion by limiting the rate of rise of the input current. The bus reactor is wired to the Drive (+1) and (+2) DC bus terminals to provide the equivalent impedance of a 3% input reactor. This option is only used on the low end of the horsepower range where DC bus reactors are not a standard Drive component (25 HP and below @ 208 VAC, 25 HP and 30 HP and below @ 480 VAC.) Option Y...
Control/Operator is equipped with 6 LED illuminated selector keys: Hand, Off, Auto, Drive Select, Bypass Select and Drive Test. The E7N also features 11 other status LED indicators: Control Power, Drive Ready, Drive Run, Drive Fault, Bypass Run, Motor O/L, Safety Open, Damper/BAS Interlock, Smoke Purge, Auto Transfer and Auto Run. The membrane over the Drive keypad is non-removable on these Bypass units (In order to use the keypad copy function on a Bypass unit - order a separate keypad, part number CDR001115).
Page 21
This disconnect switch DOES NOT provide branch short circuit protection. A device to provide branch short circuit protection MUST be provided by others upstream of the E7N Bypass unit. Fig 1.5 Disconnect Handle Positions – OFF, ON Shown in the “OFF” position Fig 1.6 Disconnect Handle Positions –...
Internal Bypass Panel Control Wiring Terminal Strips TB1 - TB5 PCB A3 Control Power Transformer “G” Option Bypass Contactor Load Connections Overload Relay Output Contactor Circuit Breaker “Disconnect” Line Connections Fig 1.7 Internal Bypass Panel TB4, TB5 and Terminal PE Jumpers J2 and J3, Analog Output Signal Level TB1, TB2 and TB3...
Page 23
Contactors The Bypass is a “2 contactor” or “3 contactor” Bypass circuit employing IEC rated contactors in an electrically interlocked arrangement to allow mutually exclusive operation in Drive or Bypass modes. The control logic and “soft start” characteristic of the Drive limit the Drive input and output contactors to motor FLA current or less.
Page 24
1.9). The factory default is shown on the wiring diagram in Chapter 2 or Schematic diagram DS.E7N.01. DIP switches S1, S2, S3 and S4 allow the user to configure various project specific functions of the E7N including: • Serial Communication terminating resistor •...
Page 25
DIP Switches are “ON” when moved toward the enclosure door. DIP Switch S1 example Fig 1.10 DIP Switches S1 to S4 for Drive/Bypass Operational Configuration Physical Installation 1 - 14 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
Exterior and Mounting Dimensions Fig 1.11 Enclosure 1 for up to 10 HP, 208 VAC and up to 20 HP, 480 VAC NEMA 1 Physical Installation 1 - 15 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
Page 27
Fig 1.12 Enclosure 2 for 15 ~ 25 HP, 208 VAC and 25 ~ 50 HP, 480 VAC NEMA 1 Physical Installation 1 - 16 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
Checking and Controlling Installation Site Install the Bypass unit as described below and maintain the specified operating conditions. Installation Site Location of the Bypass unit is important to achieving proper performance and design operating life. Install the Bypass unit as close as possible to the motor.
Controlling the Ambient Temperature To enhance the reliability of operation, the Bypass unit should be installed in an environment free from extreme temperature variations. Do not store this Technical Manual or any other documents on the top surface of the Bypass unit, they may cover the heat sink cooling air discharge opening and cause the unit to overheat.
Chapter 2 Electrical Installation This chapter describes wiring and the electrical installation process for a Drive and Bypass unit. Termination Configuration - Power Wiring ........2 Field Wiring, Pressure Wire Connector, Wire Type, Range and Tightening Torque Specifications ........3 Cable Length between Drive and Motor ........4 Grounding ..................5 Wire Routing ................6 E7 Drive Main Circuit Configurations 208 VAC ......7...
Termination Configuration - Power Wiring The input disconnect switch is located in the upper right hand side of the Bypass unit. The three phase input power connection is made to the input terminals of the disconnect. See Figure 2.1 for a representative example. The OverLoad Relay (OLR) is mounted to the contactor assembly or back panel (depending on rating), just above the bypass contactor.
Field Wiring, Pressure Wire Connector, Wire Type, Range and Tightening Torque Specifications Determine the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage. Line voltage drop is calculated as follows: IMPORTANT Line voltage drop(V) = √3 x wire resistance (Ω/km) x wire length (m) x current (A) x 10 Prior to removing any protective cover or wiring any part of the Drive, remove all power sources, including main input power and control circuit power.
Cable Length between Drive and Motor The Bypass unit should be installed as close as possible to the motor to minimize the length of load side power cable needed between the Drive and the motor. If the cable between the Drive and the motor is long, the high-frequency leakage current will increase, causing the Drive output current to increase as well.
Grounding Drive and Motor Ground Wire Landing The Drive ground lug (terminal ) is connected to the enclosure. The enclosure ground lug must be connected to earth ground. See Figure 2.1. The Drive has a second ground lug to accept the motor ground lead. Ground Wiring Precautions Observe the following precautions when connecting the ground wire: 208 VAC Drives should have a ground connection with resistance of less than 100 Ω..
2. Control power is supplied internally from the main circuit DC power supply for all Drives. 3. Consult your Yaskawa representative before using 12-pulse rectification. E7 Drive Main Circuit Configurations 480 VAC Table 2.3 Drive Main Circuit Configurations...
Control Wiring Bypass Field Control Wire Landing The Bypass field control wiring is terminated on the control PCB A2, Terminal blocks TB1 through TB5. The terminal desig- nations are labeled on the enclosure, adjacent to PCB A2 (see Figure 2.4). Route the control wiring as shown in Figure 2.3. Fig 2.4 TB1 Control Terminal Locations, All Models Electrical Installation 2 - 8 Artisan Technology Group - Quality Instrumentation ...
Contacts for customer use are provided and wired to TB1 and TB2 as follows for use as annunciators of Bypass unit operation. All are 5 amp at 120 VAC contacts. Table 2.4 Output Relays - Factory Defaults Function Name (E7N-00) Terminal Block Terminals Type...
On power up the E7N will display a red “Safety Open” LED in the “System Status” area of the front control panel if a nor- mally closed “Safety Circuit” has not been installed between TB1-1 and TB1-9 on PCB A2. This condition will prevent Drive or Bypass operation.
Page 42
When a Run command is received in HAND or AUTO mode, the E7N will display a red “Damper/BAS” LED in the “System Status” area of the front control panel. This condition will prevent Drive or Bypass operation. 1 of 3 items needs to be done before the motor can be started: 1) Install a “BAS Interlock Circuit”...
S1-2 and Drive parameter H3-08. TB5-9 is also an analog input terminal, it is always connected to Drive terminal A2. See Table 2.8, Figure 2.5 and Schematic Diagram DS.E7N.01 for clarification of the analog input configuration and applica- tions.
Page 44
Analog Input PCB A2 Configuration Fig 2.5 Analog Input PCB A2 Configuration Analog Input (Drive Speed Control Circuit) Wiring Keep this lead length as short as possible (50 m max.) to maintain signal quality. Insulated twisted shielded pair wire (2 con- ductor # 18 ga, Belden 8760 or equivalent) is required.
Analog Outputs Two analog outputs are provided, both can be configured for a signal level of 0 to 10 VDC or 4 to 20 mA. The signal level is controlled by the position of jumpers J2 and J3 (see Figures 1.8 and 1.9 for location) on Control PCB A2 and by the values selected for Drive parameters H4-07 and H4-08.
0: Modbus (APOGEE) H5-09 (Error Time) For co-ordination with other E7 Technical Manuals, the table below provides the equivalency between E7N Control PCB A2 terminal designations and E7 Drive terminal designations used in TM.E7.01, TM.E7.02, TM.E7.21, TM.E7.22 and TM.E7B.01. Table 2.12 Serial Communications Terminal Designation Cross Reference...
Page 47
Terminating Resistor The terminating resistance must be turned ON only if the Drive is at the very end of the Serial Communication chain. Set the terminating resistance by turning ON DIP switch S1-1. Fig 2.7 Terminating Resistor 1. Separate the communication cables from the main circuit cables and control circuit wiring. 2.
[Note: Smoke purge overrides all other control inputs and selector buttons. Smoke purge operation can only be terminated by opening the contact closure at terminal TB1-5 or by opening the disconnect switch (S1 on schematic DS.E7N.01).] Multi-Function Digital Inputs The Bypass 120 VAC logic circuit is interconnected with the Drive multi-function digital input terminals to allow a single customer interface to control both Drive and Bypass circuits.
DIP Switch Programmable Functions Summary TABLE 2.13 DIP Switch Functions SETTINGS FACTORY POS. DESCRIPTION SWITCH SETTING SERIAL COMMUNICATIONS TERMINATING RESISTANCE SEE TABLE 5.2 DRIVE ANALOG INPUT 2 (A2) SIGNAL (H3-08="0", FOR 0-10VDC) 4-20MADC 0-10VDC TB3(3) CONNECTED TO DRIVE ANALOG INPUT 2 (A2) TB3(3) CONNECTED TO DRIVE ANALOG INPUT 1 (A1) AUTO TRANSFER TO BYPASS UPON A DRIVE FAULT ACTIVE...
Table 2.14 Terminal Numbers and Wire Sizes (Same for all Bypass Units) Possible Recommended Tightening Wire Sizes Wire Size Terminal Torque Terminals Wire Type Screws lb.-in. (N•m) TB1-1 to 14 Stranded TB2-1 to 6 Phoenix 4.2 to 5.3 wire: TB3-1 to 4 (0.5 to 0.6) 26 to 16 (0.75)
Bypass Control Circuit Terminal Functions The functions of the control circuit terminals are shown in Table 2.15. Table 2.15 Bypass Control Circuit Terminals Type Signal Name Function Signal Level TB1-1 NC Safety Circuit Fault when OPEN TB1-9 TB1-2 Auto Mode run/stop command Run when CLOSED;...
Page 53
Table 2.15 Bypass Control Circuit Terminals (Continued) Type Signal Name Function Signal Level Multi-function analog monitor 1 Frequency Output Multi-function analog output 0 to +10 VDC or 4-20 TB3-4 (Drive terminal FM) 0 to +10 VDC/100% frequency mA set by Jumper J2 Function set by and H4-07 H4-01...
Control Terminal Blocks Electronic Panel Components Bypass Control Contactors (PCB-A2) Control Xfmr Motor OL Fig 2.11 E7N Electronic Control Interconnection of Components Electrical Installation 2 - 25 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
Page 58
Chapter 3 Control Panel This chapter describes the displays and functions of the Control Panel. Digital Operator and Control Panel Display ........2 Digital Operator and H/O/A Control Panel Keys ......3 Drive Digital Operator/Keypad ........... 4 Control Panel Indicator Lights (LEDs) ........6 Selector Key Indicators...............
Digital Operator and Control Panel Display The various items included on the Digital Operator Display and Control Panel are described below. Drive Operational Status Alpha-Numeric Drive Digital LCD Digital Display Operator/Keypad Menu Indicating LCDs Drive Keypad Operator Status Indicating LEDs Drive/Bypass and HAND/OFF/AUTO H/O/A Control Keypad...
Digital Operator and H/O/A Control Panel Keys The names and functions of the Digital Operator and H/O/A Control Panel Keys are described in Table 3.1. Table 3.1 Digital Operator and H/O/A Control Panel Keys Name Function MENU Key Scrolls from one of the five main menus to the next. ESCAPE Key Returns to the display before the DATA/ENTER key was pressed.
Drive Digital Operator/Keypad Drive Operational Status Indicators The definition of the Drive operational status indicators are shown in Table 3.2. Table 3.2 Drive Operational Status Indicators Indicator Definition Lit (red) when a forward run command is input. Also lit when the Drive is in “Hand” Mode. Lit (red) when a reverse run command is input.
Page 62
Drive Run Indicator The status of the “RUN” indicator is shown in Table 3.4 when the Drive is either in the “Hand” or “Auto” mode. Table 3.4 RUN Indicator Indicator Status Description On (Red) Drive is running Blinking (Red) Drive is decelerating to a stop Drive is stopped Drive Stop Indicator The status of the “STOP”...
Control Panel Indicator Lights (LEDs) Control Power Status Indicator Table 3.6 Control Power Indicator Indicator Status Condition 3 Phase Power is applied to the Bypass unit and the control power On (Green) transformer is functioning. 3 Phase Power is disconnected from the Bypass unit or a control power transformer fuse has cleared.
Page 64
Bypass Motor OL Indicator Table 3.9 Motor OL Indicator Indicator Status Description The motor overload (S10 on schematic E7N-00) has tripped OFF de- On (Red) energizing both the Drive and Bypass Circuits. The motor overload (S10) is satisfied. Safeties Open Status Indicator Table 3.10 Safeties Open Indicator...
Page 65
Indicator Status Description On (Green) The E7N is in AUTO mode and has received a Run command at TB1-2. The E7N is not in AUTO mode or has not received a Run command when in AUTO mode. Drive Ready Indicator Table 3.14 Drive Ready Indicator...
Selector Key Indicators When off these selector key indicators simply mean that the function has not been selected. The table below describes the operation when these functions are selected and the key indicator is lit. Table 3.17 Selector Key Indicators Selector Key LED Color Function When Lit...
Fault Control Panel Indicators “Safety Open” LED (Red when Customer Safety is open) “Damper/BAS” LED (Red when Damper Circuit or BAS open) “Fault” LED (Red when Drive is faulted) “Motor O/L” LED (Red when Thermal Overload is tripped) Control Panel 3 - 10 Artisan Technology Group - Quality Instrumentation ...
Drive Main Menus The Drive’s parameters and monitoring functions are organized into groups called menus that make it easier to read and set parameters. The Drive is equipped with five menus. The five menus and their primary functions are shown in Table 3.18 and are directly available by pressing the MENU key.
Main Menu Structure The menu selection display will appear when the MENU key is pressed from a monitor or setting display. Press the MENU key from the menu selection display to switch between the menus. Press the DATA/ENTER key from the menu selection key to monitor data and from a monitor display to access the setting display.
- DRIVE - Operation Menu This menu is used for setting a speed command or monitoring values such as output frequency and output current. It is also used for displaying the fault history and the fault traces. The Drive may be limited to this menu in order to accept a run command, see parameter b1-08 in Chapter 5 and Table 5.1.
Page 71
U1 Monitor Parameter List keys to scroll through the U1 “Monitor” parameter list. Monitor Parameters U1-01 Frequency Ref U1-02 Output Freq U1-03 Output Current U1-06 Output Voltage U1-07 DC Bus Voltage U1-08 Output kWatts U1-10 Input Term Sts U1-11 Output Term Sts U1-12 Int Ctl Sts 1 U1-13...
Page 72
U2 Fault Trace Parameter List After viewing the “Monitor” parameter list, one may view the “Fault Trace” parameter list. keys to scroll through the U2 “Fault Trace” parameter list. Fault Trace Parameters U2-01 Current Fault U2-02 Last Fault U2-03 Frequency Ref U2-04 Output Freq U2-05...
- QUICK - Quick Setting Menu This menu is used to set/read a limited set of parameters in the Drive. Follow the key operations below to access the Quick Setting Menu. Example Operations Key operations in quick programming menu are shown in the following figure. Menu Selection Display Monitor Display Setting Display...
Page 74
keys to scroll through the “Quick Setting” parameter list. Parameter Parameter Name Number b1-01 Frequency Reference Selection b1-02 Run command Selection b1-03 Stopping Method Selection b5-01 PI Mode Selection b5-02* Proportional Gain Setting b5-03* Integral Time Setting b5-31* PI Unit Selection C1-01 Acceleration Time 1 C1-02...
- ADV- Programming Menu This menu is used to set/read every parameter in the Drive. Follow the key operations below to access the Programming Menu. Example Operations Key operations in advanced programming menu are shown in the following figure. Monitor Display Setting Display Menu Selection Display Function Selection Display...
Page 76
, and keys to scroll through the “Programming” parameter group list. For a complete parameter list see Appendix A. Parameter Group Functions A1 Initialization A2 User Parameters Sequence DC Braking Speed Search Delay Timers PI Control Energy Saving Accel/Decel S-Curve Acc/Dec Torque Comp Carrier Freq Preset Reference...
- VERIFY - Modified Constants (Parameters) Menu Verify menu is used to display any parameters that have been changed from their default settings in a programming menu or by autotuning. “None” will be displayed if no settings have been changed. For the initialization parameters, only A1-00 will be displayed if it has been changed.
- A.TUNE - Auto-Tuning Menu For E7 Bypass units Auto-Tuning can only be accomplished through the DriveWizard software (Part Number DWST616-C2). A free download from www.drives.com. This menu is used in non-bypass Drives to auto-tune the Drive in order to utilize the bi-directional speed search feature. Fol- low the key operations below to access the Auto-Tuning Menu.
Example of Changing a Parameter Table 3.19 provides an example of how to change parameter “C1-01” (Acceleration Time 1) from 30 sec to 20 sec. Table 3.19 Changing a Parameter in the Programming Menu Step Digital Operator Display Description Number Power supply turned ON.
Page 80
Chapter 4 Start Up and Operation This chapter describes the procedures to prepare for and conduct the E7N Drive and Bypass unit start up. Start Up Introduction ..............2 The Safety Interlock Circuit at Power Up ........2 The BAS Interlock Circuit at Power Up ........3 Bypass Unit Start Up Preparation ..........
The Safety Interlock Circuit at Power Up On power up the E7N will display a red “Safety Open” LED in the “System Status” area of the front control panel if a normally closed “Safety Circuit” has not been installed between TB1-1 and TB1-9 on PCB A2. This condition will prevent Drive or Bypass operation.
The BAS Interlock Circuit at Power Up When a Run command is received in HAND or AUTO mode, the E7N will display a red “Damper/Bas” LED in the “System Status” area of the front control panel. This condition will prevent Drive or Bypass operation.
Note: These instructions assume that all jumpers and DIP switches are in the factory default position as defined by schematic diagram DS.E7N.01. 1. Review this Bypass Technical Manual and any option instructions and schematics shipped with the Drive and Bypass unit.
BYPASS UNIT START UP PROCEDURE (Please review “Bypass Start Up Preparation” on page 4-4) The front control panel has a digital alpha/numeric display and keypad, in the upper portion, for Drive operation and program- ming. The row of LEDs above the alpha/numeric display indicate Drive operational status. The REMOTE SEQ and REF LEDs in this row are always lit in most Bypass unit applications of the E7 Drive (See Chapter 3 for an explanation).
Page 85
2. Apply power to the Drive and Bypass package. Using a VOM, ensure that all three phases are present and that the input voltage is correct for the system being set up. When power is applied to the E7N unit, the control logic will briefly (<3 seconds) self test all the control panel operating mode LEDs, located on the lower half of the control panel.
Page 86
TB3-1 of the E7N. See the connection diagram on page 1 of the E7N Bypass unit schematic E7N-00 (or Chapter 5 in this manual). [Note: The factory default is 4-20 mA, to change to 0 to 10 VDC adjust parameter H3-08 to “0: 0-10VDC”...
Page 87
If the rotation direction in Bypass is correct, skip the rest of this step. If not, carry out the following corrections: Turn OFF the incoming power feed to the E7N unit. Since the correct rotation in Drive mode was previously established, do not change any output wires at the motor.
Page 88
Notes: Start Up and Operation 4 - 9 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
Bypass Unit Operation Description (For selector key positions, control inputs and DIP switch selectable functions.) The Bypass has two modes of operation: Bypass and Drive. When in the Bypass mode the connected motor is run directly from the incoming AC line, whereas in Drive mode the motor is run from the Drive output. The DRIVE Select and Bypass Select keys located on the front panel determine the operating mode.
Page 90
Control Panel LEDs Status LEDs Selector Button LEDs Drive Keypad LEDs Drive Bypass Smoke Drive Bypass Drive Auto/Remote Purge Ready Fault Motor O/L Select Select HAND AUTO Test ALARM STOP Flash Flash Flash Flash Flash Flash Flash Flash Flash Flash Flash Flash Flash...
For additional influences on the Drive behavior in Drive operating mode, consult Table 5.1 and Table 5.2. These tables explain the settings of Drive parameters required by the Bypass logic (Table 5.1) and those that are also dependent upon the control options present on the unit (Table 5.2).
Page 92
Drive or Bypass will return to operation. On power up the E7N will display a red “Safety Open” LED in the “System Status” area of the front control panel if a normally closed “Safety Circuit” has not been installed between TB1-1 and TB1-9 on PCB A2. This condition will prevent Drive or Bypass operation.
Contact Closure Inputs Auto Mode Run/Stop Contact Input TB1-3 and TB1-4 are input terminals used for the Run/Stop command when in the AUTO mode. When these input contacts close, the unit will begin running. When the contacts reopen, the unit will cease running.
Page 94
Chapter 5 Programming This Manual contains descriptions of all parameters in the Drive that may be useful in Bypass applications. Parameters are listed in alpha-numerical order. Parameter number and name, along with a detailed description and its settings are described on the following pages.
LCD Display Selections Programming Instructions for Individual Drive Parameters: The discussions of individual Drive parameters in Chapter 5 are descriptive of the basic E7N unit without any options that would effect the programming of the E7 Drive. Programming for Various Configuration and Options: Tables 5.1 and 5.2 and the section titled “Discussion of Table 5.2 Option-Dependent Bypass Parameter Settings”...
Page 96
Only Drive terminals A1, A2, S6, S7 and SN are available for other uses. They have been brought out to terminals on the E7N PCB A2: Drive Terminals Correspondence to E7N Terminals Drive E7N PCB A2 Drive Function E7N PCB A2...
Bypass Unit Basic Programming Parameters The basic Drive programming for a Bypass unit is different from that of a Drive installation without the Bypass option. Several Drive parameters have been programmed at the factory to meet the needs of the Bypass logic circuit. See Table 5.1 below, the highlighted parameters are required by the Bypass logic circuit.
Page 98
Table 5.1 Bypass Parameter Settings (Continued) SETTING OPTIONAL LCD PARAMETER UNITS DESCRIPTION KEYPAD DISPLAY Drive NUMBER For Bypass For Bypass Setting Default L5-01 10.0 Number of Re-start Attempts – Sets the number of Num of Restarts / (0-10) times the Drive will perform an automatic re-start L5-03 Maximum Restart Time After Fault –...
Page 99
Table 5.2 Option Dependent Bypass Parameter Settings HAND Speed Drive Terminal A2 Sig- Parameters Effected by Options Specified and Settings Command nal Level via TB3-3 or AUTO PCB DIP PCB DIP Source TB5-9 Options Switch S1 Switch S4 Specified Run/Stop Speed H1-02 H1-03...
TB3-3 to connect to Drive terminal A1 by placing DIP switch S1-3 in the Off position and DIP switch S1-4 in the On position: For an E7N with no options, as in line 2 of Table 5.2, change to have H3-09 = 2 and ensure that H3-13 = 1 (all other parameters per line 2 of Table 5.2) For an E7N with serial communications, as in lines 4, 5 and 6 of Table 5.2, change b1-01 = 1, H3-09 = 2, and...
Page 101
Options - P "Pneumatic Pressure Transducer"; Bypass with pneumatic input for speed control: Hand mode speed command from Keypad/Operator. Auto mode speed command input signal from the pneumatic transducer, or 4-20 mA applied to Terminal TB5-9 (Drive terminal A2). Auto mode run/stop contact closure for Drive and Bypass applied to terminals TB1-2 and TB1-9. Significant Drive Operational Result Parameter Setting...
Page 102
Options - J, U, V or L "Serial Communications"; Bypass with serial communication for run/stop control and speed monitoring: Hand mode speed command from Keypad/Operator. Auto mode speed command input signal, 0-10 VDC applied to Terminal TB3-3 (Drive terminal A2). Auto mode run/stop command for Drive from serial communication.
Drive Parameters A1 Initialization The initialization group contains parameters associated with initial setup of the Drive. Parameters involving the display language, access levels, initialization and password are located in this group. A1-00 Select Language (Optional LCD keypad only) Setting Description English (factory default) Japanese Deutsch...
Page 104
The Drive can be set back to one of three default states via the A1-03 parameter. Note: The E7N application of the Drive employs “2-wire” control. 1. User Initialization – 1110:The modified Drive parameters are returned to the values selected as user settings. User settings are stored when parameter o2-03= “1: Set Defaults”.
A1-04 Password Entry Setting Range: 0 to 9999 Factory Default: 0 If parameters A1-01 through A1-03 and all of the A2 parameters are locked (unchangeable) they can be unlocked by entering the correct password number into A1-04. Once the correct password number is entered and the specified parameters are unlocked, a 2-Wire or 3-Wire initialization will reset the password to 0000.
Page 106
If you want the Drive to receive the speed command from serial communication: Set the parameters indicated in Table 5.2 for the desired serial communication option. Connect the RS-485/422 serial communications cable to terminals TB4-3 (R+), TB4-4 (R-), TB4-1 (S+), and TB4-2 (S-) on the E7N PCB A2. The HAND/OFF/AUTO selector must be in the AUTO position.
Page 107
When the output frequency has dropped below the DC Injection Start Frequency in b2-01 (Default = 0.5HZ) DC current will be injected in the motor at a level determined by b2-02 (50% Default). The DC Injection condition will occur for the time specified by b2-04 (0.0 Default), to establish the end point of the ramp.
Page 108
2:DCInj to Stop: When the Run command is removed, the Drive will Baseblock (turn off its output) for the Minimum Base- block Time (L2-03). Once the Minimum Baseblock Time has expired, the Drive will inject DC current into the motor wind- ings to lock the motor shaft.
Page 109
It’s not immediately apparent how to program a reverse run function on the E7N. Cooling tower defrost initiated by a BAS con- tact closure is an example. Here is one way to accomplish this: As the unit ships from the factory, Drive terminals S6 and S7 are the only ones available for customer use.
b1-08 Run Command Selection During Programming Setting Description Disabled Enabled (factory default) As a convenience to the user, the Drive will respond to a Run input even when the digital operator is being used to adjust parameters. If it is necessary that external Run commands not be recognized while the Drive is being programmed, set b1-08= “0: Disabled”.
Page 111
b2-02 DC Injection Braking Current Setting Range: 0 to 100% Factory Default: 50% The level of DC Injection Braking Current affects the strength of the magnetic field attempting to lock the motor shaft. Increasing the level of current will increase the amount of heat generated by the motor windings and should only be increased to the level necessary to hold the motor shaft.
b3 Speed Search The Speed Search function allows the Drive to determine the speed of a motor shaft that is being driven by rotational inertia. Speed Search will allow the Drive to determine the speed of the already rotating motor and begin to ramp the motor to a set speed without first having to bring it to a complete stop.
Page 113
AC power supply Set frequency Start using reference speed detected Output frequency Output current 10 ms Minimum baseblock time (L2-03) x 0.75 *1 *1 Baseblock time may be reduced by the output frequency immediately before the baseblock. Minimum baseblock time (L2-03) x 0.75*1 the motor waits for the *2 After AC power supply recovery, motor waits for the minimum Speed Search Wait Time (b3-05).
Page 114
Deceleration time set in b3-03 Run command Maximum output Set frequency frequency or reference set frequency Output frequency Speed search current level b3-02 Output current Search Delay Time (b3-05). * Lower limit is set using Speed Search Time (b3-05). Minimum baseblock time (L2-03) Fig 5.10 Speed Search (Current Detection Method) at Startup AC power supply...
Page 115
b3-02 Speed Search Deactivation Current Setting Range: 0 to 200% of Drive rated output current Factory Default: 120% of Drive rated output current When using the current detection method of Speed Search, parameter b3-02 sets the current level that will determine when the search is complete and the rotor and output speeds match.
b5 PI Function The capability to accept an analog signal as feedback for a PI (Proportional + Integral) control function is built into the Drive. D1-04 Frequency Reference using multi-step Sleep function command selection b5-21 D1-02 b1-01 b5-16 on/off Delay Frequency reference D1-01 b5-01=0...
Page 117
Table 5.3 PI Control Parameter Settings in E7N Bypass Units SETTING OPTIONAL LCD PARAMETER Bypass & PI Bypass KEYPAD DISPLAY UNITS DESCRIPTION NUMBER Control Default For Bypass Setting b1-01 SEE TABLE Frequency Reference Selection – Selects the Reference Source / Terminals...
Page 118
Table 5.4 Option Dependent Bypass Parameter Settings with PI Control HAND Speed Drive Terminal A2 Parameters Effected by Options Specified and Command Signal Level via TB3-3 AUTO Settings Source or TB5-9 PCB DIP PCB DIP Options Switch S1 Switch S4 Speed or Specified Run/Stop...
Page 119
Optional LCD Digital Operator and Control Panel Display for PI Control In Table 5.5, the o1-0X parameter listed setup the Drive display to indicate 3 variables for PI control as in Figure 5.14 when the HAND/OFF/AUTO selector is in AUTO . Table 5.5 parameter for optional LCD display setup for PI control.
Page 120
For project specific PI control tuning see the PI Control (b5-XX) parameters in this chapter. Tables 5.3 and 5.4 provide the basic configuration for PI Control from a Drive in an E7N Bypass unit. The b5-XX parameters are defaulted to a good starting point for most HVAC applications. Final adjustment to some of the b5-XX parameters for the project at hand may be required.
Page 121
Options - J, U, V or L "Serial Communications"; Bypass with PI Control and serial communication for run/stop control and Setpoint input: Hand mode speed command from Keypad/Operator. Auto mode PI Setpoint input signal from serial communication. Auto mode run/stop command for Drive from serial communication. Auto mode run/stop command for Bypass from serial communication.
Page 122
The analog feedback to the Drive for the PI control is via the Drive A2 terminal. The Drive must be programmed (H3-09= “B: PI Feedback”) to use terminal A2 as feedback for the PI functionality of the Drive. The PI setpoint can be configured to come from one of many different inputs or parameters. The table below describes the options for originating the PI setpoint.
Page 123
The Integral factor of PI functionality is a time-based gain that can be used to eliminate the error (difference between the setpoint and feedback at steady state). The smaller the Integral Time set into b5-03, the more aggressive the Integral factor will be.
Page 124
b5-08 PI Primary Delay Time Constant Setting Range: 0.00 to 10.00 Seconds Factory Default: 0.00 Seconds Acts as a time based filter that lowers the responsiveness of the PI function, but also makes the function more stable when the setpoint varies rapidly or when the feedback is noisy. b5-09 PI Output Level Selection Setting Description...
Page 125
b5-13 PI Feedback Loss Detection Level Setting Range: 0 to 100% Factory Default: 0% b5-14 PI Feedback Loss Detection Time Setting Range: 0.0 to 25.0 Seconds Factory Default: 1.0 Seconds The Drive interprets feedback loss whenever the feedback signal drops below the value of b5-13 and stays below that level for at least the time set into b5-14.
Page 126
b5-17 PI Accel/Decel Time Setting Range: 0.0 to 25.5 Seconds Factory Default: 0.0 Seconds This is a soft start function that is applied to the PI setpoint analog input. Instead of having nearly instantaneous changes in signal levels, there is a programmed ramp applied to level changes. When changing setpoints the error can be limited by gradually ramping the setpoint through the use of parameter b5-17.
Page 127
If the monitors seem more natural in terms of percentage, set b5-20= 1. If the monitors are easier to work with when displaying the equivalent synchronous RPM, set b5-20= [the number of motor poles]. If another engineered unit, such a fpm or cfm, is desired, set b5-20= xxxxx where X X X X X Digit 5 Digit 4 Digit 3 Digit 2 Digit 1 Digits 1 through 4 set the desired number to be displayed at 100% speed.
Page 128
b5-22 PI Snooze Level Setting Range: 0 to 100% Factory Default: 0% b5-23 PI Snooze Delay Time Setting Range: 0 to 3600 Seconds Factory Default: 0 Seconds b5-24 PI Snooze Deactivation Level Setting Range: 0 to 100% Factory Default: 0% The Snooze Function is a variation on the Sleep Function.
Page 129
b5-26 PI Maximum Boost Time Setting Range: 0 to 3600 Seconds Factory Default: 0 Seconds Associated with the Snooze Function. In cases where the temporary PI Setpoint (intended PI setpoint + PI Setpoint Boost) cannot be reached within the PI Maximum Boost Time (b5-26), the Setpoint Boost is interrupted and the Drive output is turned off.
b5-29 PI Square Root Gain Setting Range: 0.00 to 2.00 Factory Default: 1.00 A multiplier applied to the square root of the feedback. b5-30 PI Output Square Root Monitor Selection Setting Description Disabled (factory default) Enabled If the PI Function is regulating the flow of a closed loop system by using a pressure feedback, it may be convenient to view the square root of the PI output using monitor U1-37.
C1 Accel/Decel C1-01 Acceleration Time 1 C1-02 Deceleration Time 1 C1-03 Acceleration Time 2 C1-04 Deceleration Time 2 Setting Range: 0.0 to 6000.0 Seconds Factory Default: 30.0 Seconds C1-01 (Acceleration Time 1) sets the time to accelerate from zero to maximum speed (E1-04). C1-02 (Deceleration Time 1) sets the time to decelerate from maximum speed to zero.
d1 Preset References d1-01 Frequency Reference 1 d1-02 Frequency Reference 2 d1-03 Frequency Reference 3 d1-04 Frequency Reference 4 Setting Range: 0.00 to E1-04 Value Factory Default: d1-01 = 10.00 Hz d1-02 = 6.00 Hz d1-03 = 0.00 Hz d1-04 = 0.00 Hz d1-01 and d1-02 are special parameter settings required by the Bypass logic circuit.
Page 133
As shown in Table 5.8, it is possible to use analog inputs in place of Frequency Reference 1 and Frequency Reference 2. If b1-01= “1: Terminals” then the analog input A1 will be used instead of Frequency Reference 1 for the first preset speed. If b1-01= “0: Operator”, then Frequency Reference 1 will be used.
d2 Reference (Speed Command) Limits d2-01 Frequency Reference Upper Limit Setting Range: 0.0 to 110.0% Factory Default: 100.0% d2-02 Frequency Reference Lower Limit Setting Range: 0.0 to 110.0% Factory Default: 0.0% The use of parameters d2-01 and d2-02 places limitations on the speed command that the Drive will accept. The parameters are set in units of percentage of the maximum frequency (E1-04) and provide limits on any remote speed command input.
Page 135
d3 Jump Frequencies d3-01 Jump Frequency 1 d3-02 Jump Frequency 2 d3-03 Jump Frequency 3 Setting Range: 0.0 to 200.0 Hz Factory Default: 0.0 Hz d3-04 Jump Frequency Width Setting Range: 0.0 to 20.0 Hz Factory Default: 1.0 Hz In order to avoid continuous operation at a speed that causes resonance in driven machinery, the Drive can be programmed with jump frequencies that will not allow continued operation within specific frequency ranges.
d4 Sequence d4-01 MOP Reference Memory Setting Description Disabled (factory default) Enabled The Drive offers the capacity to change the speed command much the way a Motor Operated Potentiometer (MOP) would. Using programmed digital inputs configured as MOP Increase (H1-0x= 10) and MOP Decrease (H1-0x= 11), the Drive will increase the speed command whenever the MOP Increase input is closed and decrease the speed command whenever the MOP Decrease is closed.
E1 V/f Pattern E1-01 Input Voltage Setting Setting Range: 155.0V to 255.0V (208V/240V Models) 310.0V to 510.0V (480V Models) Factory Defaults: 208.0V (208V Models) 240.0V (240V Models) 480.0V (480V Models) Set the Input Voltage parameter (E1-01) to the nominal voltage of the connected AC power supply. This parameter adjusts the levels of some protective features of the Drive (i.e.
Page 139
E1-05 Maximum Output Voltage Setting Range: 0.0 to 255.0V (208V/240V Models) 0.0 to 510.0V (480V Models) Factory Defaults: 208.0V (208V Models) 230.0V (240V Models) 460.0V (480V Models) E1-06 Base Frequency Setting Range: 0.0 to 200.0 Hz (settings above 120.0 Hz are currently not supported) Factory Default: 60.0 Hz E1-07 Mid Output Frequency A Setting Range:...
To set up a custom V/f pattern, program the points shown in the diagram below using parameters E1-04 through E1-13. Be sure that the following condition is true: E1-09 ≤ E1-07 ≤ E1-06 ≤ E1-11 ≤ E1-04 Max Voltage E1-05 Mid Voltage B E1-12 Base Voltage E1-13 Mid Voltage A E1-08...
E2-03 No Load Current Setting Range: Model Dependent (see appendix B) Factory Default: Model Dependent Set E2-03 to the motor no-load current at rated voltage and rated frequency. Consult the motor manufacturer for the proper value if the no load current is not stated on the motor nameplate. F6 Com OPT Setup ®...
F6-05 Current Scaling via Communication Option PCB Setting Description A Display (factory default) 100%/8192 (Drive Rated Current) A communication option card can read the Drive’s DPRAM to access the current monitor. The format of the current reading in the DPRAM will be determined by parameter F6-05. F6-05= “0: A Display”...
Page 143
The Drive has five multi-function contact digital inputs. By programming parameters H1-01 through H1-05, the user can assign specific functions to each input. Below is a table with a complete list of all of the digital input functions. The programming manual has a more detailed description of each of the functions.
Page 144
The following table details which reference is active based on the status of the Multi-step Ref 1 and Multi-step Ref 2 inputs: Table 5.11 Digital Input Functions Terminal Terminal Terminal Programmed Programmed Programmed as Preset Speed Details as Multi-step as Multi-step Jog Reference Reference 1 Reference 2...
Page 145
Table 5.12 Option/Inv Function Input Status Run and Speed Command Source OPEN From the control circuit and analog input terminals CLOSED From Serial Com port (R+,R-,S+, and S-) (embedded protocols) To switch the command source between the serial communication port and the control circuit terminals be sure to program the following parameters: •...
Page 146
H2 Digital Outputs H2-01 Drive Terminal M1-M2 Function Selection H2-02 Drive Terminal M3-M4 Function Selection Setting Range: 0 to 3B Factory Default: H2-01= “0: During Run 1” H2-02= “3B: Run Src Com/Opt” H2-01 and H2-02 are two of the special parameter settings required by the Bypass logic circuit. See Table 5.1. The Drive has two multi-function outputs.
H3 Analog Inputs H3-02 Drive Terminal A1 Gain Setting Setting Range: 0.0 to 1000.0% Factory Default: 100.0% The addition of another input signal on terminal A1 to the Drive and Bypass unit, after shipment to the job site, would be the only reason for changing this parameter.
Page 148
Gain =200% 100% Bias = 0% 12mA 20mA Analog Input Level Analog Input Signal Fig 5.25 Output Frequency as Commanded via Analog Input with Increased Gain Setting Adjustment of the bias setting will likewise adjust the speed command that is equivalent to the minimum analog input level (0Vdc or 4mA).
Page 149
A2 analog input (E7N Terminal TB3-3 or TB5-9). The A2 analog input can accept either a 0–10 Vdc or 4-20 mA signal as a reference. The E7N also has a DIP switch (S1) on the PCB A2 that must be set for the proper reference signal into the A2 analog input.
Page 150
PI Differential Not Used The Drive A2 analog input (E7N Terminal TB3-3 or TB5-9) can be programmed to perform many different functions. The setting of parameter H3-09 determines which of the following functions the A2 analog input will perform. Function: Aux Reference...
Page 151
H3-10 Drive Terminal A2 Gain Setting Setting Range: 0.0 to 1000.0% Factory Default: 100.0% H3-11 Drive Terminal A2 Bias Setting Setting Range: -100.0% to +100.0% Factory Default: 0.0% Parameters H3-10 and H3-11 perform the same function for the A2 analog input that parameters H3-02 and H3-03 perform for the A1 analog input.
Page 152
H3-13 Master Frequency Reference Terminal Selection Setting Description Main Fref= A1 (factory default) Main Fref= A2 Parameter H3-13 allows the programmer to select which analog input will serve as the Speed Command input when “Termi- nals” are selected as the Auto Mode Speed source (b1-01= “1: Terminals”), or Terminal is selected as the reference source for the Hand mode (b1-12= “1: Terminals”).
L2 Momentary Power Loss Ride-thru Function When momentary power loss recovery is enabled (L2-01 ≠0), a speed search is executed to catch the potentially spinning motor shaft. This speed search will occur regardless of the setting of b3-01 “Speed Search Selection”. L2-01 Momentary Power Loss Detection Selection Setting Description...
L3 Stall Prevention L3-01 Stall Prevention Selection During Accel Setting Description Disabled General Purpose (factory default) Intelligent L3-02 Stall Prevention Level During Accel Setting Range: 0 to 200% of Drive rated output current Factory Default: 120% of Drive rated output current The stall prevention during acceleration function adjusts the acceleration time in order to prevent OC fault trips during acceleration.
Page 155
The following figure demonstrates acceleration when L3-01= “1: General Purpose”. a - Set accel time b - Accel time is extended Output Frequency L3-02 Output Current TIME Fig 5.31 Time Chart for Stall Prevention During Acceleration The L3-02 parameter is set as a percentage of the Drive rated output current. If the motor capacity is small compared to the Drive’s capacity, or if the motor stalls during acceleration, lower the set value of L3-02.
Page 156
a - Set decel time b - Decel time is extended Output Frequency DC Bus 380/660/760 Vdc Voltage TIME Fig 5.32 Time Chart for Stall Prevention During Deceleration L3-05 Stall Prevention Selection During Running Setting Description Disabled Decel Time 1 (factory default) Decel Time 2 L3-06 Stall Prevention Level During Running Setting Range:...
L4 Speed Command Loss Detection L4-05 Frequency Reference Loss Detection Selection Setting Description Disabled (factory default) Enabled @ % of PrevRef L4-06 Frequency Reference at Loss of Frequency Reference Setting Range: 0.0 to 100.0% of previous speed command Factory Default: 80.0% of previous speed command The Drive can be configured to compensate for the loss of its external speed command.
L5 Fault Restart L5-01 Number of Auto Restart Attempts Setting Range: 0 to 10 Factory Default: 10 L5-02 Auto Restart Operation Selection Setting Description No Flt Relay (factory default) Flt Relay Active L5-03 Maximum Restart Time After Fault Setting Range: 0.5 to 600.0 Seconds Factory Default: 600.0 Seconds All major faults will cause the Drive to stop.
Page 159
The setting of parameter L5-02 determines whether the fault output (MA-MB) will be closed during an auto restart attempt. The setting of L5-02 can be important when interfacing the Drive with other equipment. The following faults will allow the Auto Restart function to initiate: •...
L6 Torque Detection L6-01 Torque Detection Selection 1 Setting Description Disabled (factory default) OL@SpdAgree - Alm OL At Run -Alm OL@SpdAgree - Flt OL At Run - Flt UL@SpdAgree - Alm UL at Run - Alm UL@SpdAgree - Flt UL At Run - Flt L6-02 Torque Detection Level 1 Setting Range: 0 to 300% of Drive rated output current...
Page 161
After selecting the proper detection scheme the Torque Detection Level (L6-02) must be specified. If the current level read by the output current transformers rises above (overtorque) or drops below (undertorque) this level, and remains there for at least the Torque Detection Time (L6-03), then the Torque Detection Function will change the state of any digital output configured for Torque Detection (H2-01/H2-02= “B: Trq Det 1 N.O.”, or “17: Trq Det 1 N.C.”).
L8 Hardware Protection L8-01 Internal Dynamic Braking Resistor Protection Selection Setting Description Not Provided (factory default) Provided This parameter is not applicable for Drive operation. L8-02 Overheat Pre-Alarm Level Setting Range: 50 to 130 Factory Default: 95 L8-03 Overheat Pre-Alarm Operation Selection Setting Description Ramp to Stop (Decel Time C1-02)
Page 163
L8-11 Heatsink Cooling Fan Operation Delay Time Setting Range: 0 to 300 Seconds Factory Default: 300 Seconds Parameters L8-10 and L8-11 allow the Drive programmer to customize the heatsink cooling fan operation. Parameter L8-10 determines whether the cooling fans are always ON whenever the Drive is powered (L8-10= “1: Fan Always On”) or if the cooling fans are only ON when the Drive is in a Run condition (L8-10= “0: Fan On-Run Mode”).
o1 Monitor Configuration o1-01 User Monitor Selection Setting Range: 6 to 53 Factory Default: 6 Setting Description Output Voltage (factory default) DC Bus Voltage Output Power Input Terminal Status Output Terminal Status Drive Operation Status Cumulative Operation Time Software Number Terminal A1 Input Voltage Terminal A2 Input Voltage Motor Secondary Current (I...
Page 165
o1-02 Power-On Monitor Setting Description Frequency Reference (factory default) Output Frequency Output Current User Monitor (set by o1-01) When the Drive is powered up, the display monitor is the “Power-On” monitor. The factory default “Power-On monitor” is Speed Command (U1-01). Pressing the INCREASE key once scrolls the monitors to show the next two sequential monitors, Output Frequency (U1-02), Output Current (U1-03) and User Monitor as selected by o1-01.
Page 166
o1-03 Digital Operator Display Scaling Setting Description Hz (factory default) 2 - 39 RPM (Enter the # of Motor Poles) 40 - 39999 User Display Parameter o1-03 allows the programmer to change the units in which the speed monitors and some speed parameters are displayed. The o1-03 parameter will change the units of the following: •...
Page 167
o1-05 LCD Contrast Adjustment Setting Range: 0 to 5 Factory Default: 3 The contrast setting of the LCD display of the digital operator can be adjusted by the setting of parameter o1-05. The higher the number programmed into o1-05, the darker the background will become. Set o1-05 to the value that makes the LCD the easiest to view at the normal viewing distance and angle.
o2 Key Selections o2-03 User Parameter Default Value Setting Description No Change Set Defaults Clear All The Drive gives the option of configuring any and all of the programming parameters and then saving the parameters as “User Initialization Values”. After configuring the Drive, set parameter o2-03= “1: Set Defaults”, to save the parameters to a User Initialization memory location.
Page 169
o2-06 Operation Selection when Digital Operator is Disconnected Setting Description Disabled Enabled (factory default) Leaving o2-06 enabled will cause the Drive to fault, when the digital operator is removed, even if it’s not outputting to the motor. The reset key on the digital operator will need to be pressed after reconnecting the digital operator to reset the fault and continue normal operation.
Page 170
o2-10 Cumulative Cooling Fan Operation Time Setting Setting Range: 0 to 65535 Hours Factory Default: 0 Hours The elapsed time of heatsink cooling fan operation is tracked by the U1-40 monitor. Much like the o2-07 parameter can be used to adjust or reset the Drive operation elapsed timer, parameter o2-10 can be used to adjust the time displayed by the U1-40 monitor in the event of fan replacement.
o3 Digital Operator Copy Function o3-01 Copy Function Selection The membrane over the Drive keypad also makes the keypad non-removable on Bypass units. In order to use the keypad copy function on a Bypass unit - order a separate keypad, part number CDR001115 and obtain locally a standard CAT 5 Ethernet cable.
Page 172
• Software Number (e.g. 03011 also known as FLASH ID) Yaskawa offers DriveWizard™ software that can also READ, COPY, and VERIFY Drive parameter values. DriveWizard™ lists all discrepancies between the Drive and a pre-saved parameter file when verifying is performed.
T1 Auto-Tuning Auto-Tuning can only be accomplished through the DriveWizard software (Part Number DWST616-C2). Available by download from www.drives.com. T1-02 Motor Rated Power Setting Range: 0.00 to 650.00 kW Factory Default: Model Dependent T1-04 Motor Rated Current Setting Range: Model Dependent Factory Default: Model Dependent Auto tuning is recommended to achieve optimum performance.
Page 174
Chapter 6 Diagnostics & Troubleshooting This chapter describes diagnostics and troubleshooting for the Drive and Bypass. E7N Bypass PCB and H/O/A Control Panel Diagnostics ....2 Introduction ................2 Specifications................2 Set Up for Maintenance Mode............ 2 Testing ..................3 Drive Diagnostics ................
This section describes a quick and systemic approach in troubleshooting of an E7N Bypass panel and PCB A2. The only addi- tional testing device needed will be a DVM to verify the PCB A2 interactions and connections to other devices in the E7N Bypass panel.
Testing Test all the fuses in the panel, including the two on the bypass control PCB A2. CAUTION In maintenance mode, all power or control systems connected to the bypass panel such as motors or controls will be energized for a couple of seconds to allow the wiring to be tested. If this is not desirable, these wires should be disconnected from the panel prior to any maintenance mode testing.
Page 177
Check programming of parameter H2-02. This parameter must be set to pressed; with no contact closure at TB1-2. “3B: Run Src Com/Opt” for all E7N units. See Table 5.1. Diagnostic & Troubleshooting 6 - 4 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
Page 178
The overall layout of PCB A2 is shown in Figure 6.1 for further reference. Customer Connector Connection For cable to Terminals Keypad Customer 120V Customer Circuit Fuse Configuration Switches Connectors to Panel Wiring Harnesses Connector CPLD For cable to Logic Drive Main Processor...
Field Service, Start Up Assistance, Factory Repair, Replacement Parts, and Other Support Contact Drives Technical Support for help with any of these needs. Technical Training Training is conducted at Yaskawa training centers, at customer sites, and via the internet. For information, visit www.yaskawa.com or call 1-800-YASKAWA (927-5292).
Fault Detection When the Drive detects a fault, the fault information is displayed on the digital operator, the fault contact closes, and the motor coasts to stop. (However, a fault with selectable stopping method will operate according to the stopping method selected.) •...
Page 181
Table 6.3 Fault Displays and Processing (Continued) Digital Description Cause Corrective Action Operator Display Perform a factory initialization. CPF04 Noise or spike on the control Cycle power off and on to the CPU Internal A/D Converter Fault Internal A/D Err circuit input terminals.
Page 182
Table 6.3 Fault Displays and Processing (Continued) Digital Description Cause Corrective Action Operator Display Remove power to the Drive. Connect the option board once An option board is not more. correctly connected to the con- Perform a factory initialization. CPF23 Communication Option Card trol board or an option board Option DPRAM Err...
Page 183
Table 6.3 Fault Displays and Processing (Continued) Digital Description Cause Corrective Action Operator Display Ensure the values in L6-02 and Loss of Load Detection 1 L6-03 are appropriate. Motor is underloaded. Drive output current < L6-02 for more than Loss of Load Det 1 Check application/machine the time set in L6-03 status to eliminate fault.
Page 184
Table 6.3 Fault Displays and Processing (Continued) Digital Description Cause Corrective Action Operator Display The load is too large. The Recheck the cycle time and the cycle time is too short at the size of the load as well as the accel/decel time.
Page 185
Table 6.3 Fault Displays and Processing (Continued) Digital Description Cause Corrective Action Operator Display Verify dynamic braking duty Overhauling load, extended cycle. Dynamic Braking Resistor dynamic braking duty cycle, Monitor DC bus voltage. The protection of the dynamic braking DynBrk Resistor defective dynamic braking resistor based on setting of L8-01 resistor.
Alarm Detection Alarms are Drive protection functions that does not operate the fault contact. The Drive will automatically return to its original status once the cause of the alarm has been removed. During an alarm condition, the Digital Operator display flashes and an alarm output is generated at the multi-function outputs (H2-01 to H2-02) if programmed.
Page 187
Table 6.4 Alarm Displays and Processing (Continued) Digital Description Cause Corrective Action Operator Display Verify Drive is programmed to receive the PI Feedback source signal. Check to ensure the PI Feedback PI Feedback Loss source is installed and working properly. PI Feedback source This fault occurs when PI Feedback Loss (e.g.
Page 188
Table 6.4 Alarm Displays and Processing (Continued) Digital Description Cause Corrective Action Operator Display Check the input circuit and High input voltage at R/L1, reduce the input power to within S/L2 and T/L3. specifications. DC Bus Overvoltage The deceleration time is set too DC Bus Overvolt Extend the time in C1-02.
Operator Programming Errors (OPE) An Operator Programming Error (OPE) occurs when an inapplicable parameter is set or an individual parameter setting is inappropriate. The Drive does not operate until the parameter is set correctly. (Alarm output and fault contact do not operate.) If an OPE occurs, change the appropriate parameter by checking the cause shown in Table 6.5.
Auto-Tuning Faults Auto-tuning faults are shown below. When the following faults are detected, the fault is displayed on the digital operator and the motor coasts to a stop during operation. The fault contact is not activated. Table 6.6 Auto-Tuning Displays and Processing Digital Operator Display Probable Cause Corrective Action...
Digital Operator COPY Function Faults These faults can occur occurred during the operator COPY function. Fault content is displayed on the operator. An error during the COPY function does not activate the fault contact output or alarm output. Table 6.7 Digital Operator COPY Function Faults Function Digital Operator Display Probable Causes...
Drive Troubleshooting Due to parameter setting errors, faulty wiring, etc., the Drive and motor may not operate as expected when the system is started up. If this occurs, use this section as a reference and apply the appropriate measures. If a fault is displayed on the digital operator, refer to Fault Detection, Table 6.3. If Parameter Cannot Be Set Use the following information if a Drive parameter cannot be set.
If the Motor Does Not Operate Use the following information if the motor does not operate. Ensure the digital operator is securely connected to the Drive. The motor does not operate when the HAND key on the Digital Operator is pressed. The following causes are possible: The Speed Command (Frequency Reference) is too low.
The motor stops during acceleration or when a load is connected. The load may be too high. The Drive has a stall prevention function and an automatic torque boost function, but the motor responsiveness limit may be exceeded if acceleration is too rapid or if the load is too great. Lengthen the acceleration time (CI-01) or reduce the load.
If the Motor Overheats Take the following steps if the motor overheats. The load is too high. If the motor load is too high and the motor is used when the effective torque exceeds the motor's rated torque, the motor will overheat.
If a “Stand Alone” Ground Fault Interrupter Operates When the Drive is Run The Drive performs internal switching, so there is a certain amount of leakage current. This may cause an external ground fault interrupter to operate and cut off the power supply. Whenever possible, use a ground fault interrupter with a high leakage detection level (i.e., a sensitivity current of 200 mA or greater per unit, with an operating time of 0.1 s or more), or one that incorporates high frequency countermeasures (i.e., one designed for use with Drives).
If the Motor Rotates Even When Drive Output is Stopped If the motor rotates even when the Drive is stopped, the DC injection braking may be insufficient. If the motor continues operating at low speed, without completely stopping after a stop has been executed, it means that the DC injection braking is not decelerating the motor enough.
Drive Main Circuit Test Procedure Prior to removing any protective cover or wiring any part of the Drive, remove all power sources, including main input power and control circuit power. Wait a minimum of 5 minutes after power removal, before WARNING removing any cover.
Page 199
Table 6.8 Main Circuit Test Procedure (Continued) Procedure Check 11. Place the positive (red) meter lead on terminal ⊕ 1. Place the negative (black) meter lead on terminal R/L1. Expected reading is OL displayed. 12. Place the positive (red) meter lead on terminal ⊕ 1. Input Diodes Place the negative (black) meter lead on terminal S/L2.
Page 200
Table 6.8 Main Circuit Test Procedure (Continued) Procedure Check The output transistors are used to switch the DC bus voltage to allow current to flow to the motor. 1. Set a digital multi-meter to the Diode Check setting. 2 Place the positive (red) meter lead on terminal U/T1. Place the negative (black) meter lead on terminal ⊕...
Page 201
Table 6.8 Main Circuit Test Procedure (Continued) Procedure Check The Heat Sink & Internal Cooling Fans cool the heat sink as well as the output transistor modules of the Drive. 1. Conduct a visual inspection to ensure the fan turns freely. 2.
Drive Date Stamp Information This information is used to determine when a Drive was built to see if it is within its warranty period. The date stamp is located on the lower right side of the Drive. Fig 6.2 Date Stamp Location YEA Production Manufacture Date 00.7.22...
Page 204
This chapter describes basic maintenance and inspection of the Drive and Bypass unit. Please refer to these instructions to ensure that the Drive receives the proper maintenance to maintain overall performance. E7N Maintenance ................2 Periodic Inspection ..............2 Preventive Maintenance ............3 Drive Heatsink Cooling Fan Replacement .........
E7N Maintenance Periodic Inspection Check the following items during periodic maintenance. The motor should not be vibrating or making unusual noises. • There should be no abnormal heat generation from the Drive and Bypass or motor. • The ambient temperature should be within the Drive and Bypass specification of -10 ° C to 40 ° C (14 ° F to 104 ° F).
Preventive Maintenance Table 7.3 Preventive Maintenance Inspection Points Item Check Points Every 3-6 Months Yearly Ambient Temperature Humidity Dust Environment Harmful Gas General Oil Mist Abnormal vibration or noise Equipment Main circuit & control voltage AC Power Supply Loose lugs, screws & wires Hot spots on parts Corrosion Conductors &...
Drive Heatsink Cooling Fan Replacement _ _ _ Drive Models CIMR- 20P4 thru 2018 (25 HP@ 208 V) and 40P4 thru 4018 (30 HP@ 480 V) If the Drive is mounted with the heatsink external to the enclosure, as it is in Bypass units, the cooling fan IMPORTANT can only be replaced by removing the Drive from the enclosure.
Page 208
Drive Models 4030 (40 HP and above @ 480 V) A cooling fan assembly is attached to the top inside the Drive. The cooling fan assembly includes the heat sink cooling fans and the internal cooling fan. The cooling fan(s) can be replaced without removing the Drive from the enclosure panel. Removing the Drive Cooling Fan Assembly Always turn OFF the input power before removing and installing the heatsink cooling fan assembly.
Decimal to Hex Conversion............30 NOTE 1: “Factory settings” listed in this appendix are for the Drive only. See Table 5.1 and Table 5.2 for E7N Bypass factory settings. NOTE 2: In this parameter list, the second column “Parameter Name/LCD Digital Operator Display”...
Parameter List Table A.1 Parameter List Parameter Name Parameter Setting Factory Menu Description LCD Digital Operator Range Setting Location Display Initialization Language selection for digital operator display 0: English 2: Deutsch A1-00 Language Selection 3: Francais 0 to 6 Programming Select Language 4: Italiano 5: Espanol...
Page 212
Table A.1 Parameter List (Continued) Parameter Name Parameter Setting Factory Menu Description LCD Digital Operator Range Setting Location Display User Parameter 7 – A2-07 Programming User Param 7 User Parameter 8 – A2-08 Programming User Param 8 User Parameter 9 –...
Page 213
Table A.1 Parameter List (Continued) Parameter Name Parameter Setting Factory Menu Description LCD Digital Operator Range Setting Location Display Sequence Selects the speed command (frequency reference) input source. 0: Operator - Digital preset speed d1-01 Frequency Reference 1: Terminals - Analog Input Terminal A1 (or Terminal A2 see Quick Setting b1-01 Selection...
Page 214
Table A.1 Parameter List (Continued) Parameter Name Parameter Setting Factory Menu Description LCD Digital Operator Range Setting Location Display Motor Pre-heat current in % of drive rated current. This is used to Motor Pre-Heat Current b2-09 keep the motor warm to prevent condensation and is used in 0 to100 Programming Preheat Current...
Page 215
Table A.1 Parameter List (Continued) Parameter Name Parameter Setting Factory Menu Description LCD Digital Operator Range Setting Location Display PI Primary Delay Time b5-08 Sets the amount of time for a filter on the output of the PI 0.00 to Constant 0.00sec Programming...
Page 216
Table A.1 Parameter List (Continued) Parameter Name Parameter Setting Factory Menu Description LCD Digital Operator Range Setting Location Display PI Feedback Square Root 0: Disabled b5-28 Function Selection 0 or 1 Programming 1: Enabled PI Feedback SqRt PI Square Root Gain b5-29 A multiplier applied to the square root of the feedback.
Page 217
Table A.1 Parameter List (Continued) Parameter Name Parameter Setting Factory Menu Description LCD Digital Operator Range Setting Location Display S-Curve Acc/Dec S-curve is used to further soften the starting ramp. The longer the S-curve time, the softer the starting S-Curve Characteristic at ramp.
Page 218
Table A.1 Parameter List (Continued) Parameter Name Parameter Setting Factory Menu Description LCD Digital Operator Range Setting Location Display Reference Limits Determines maximum speed command, set as a percentage of Frequency Reference Upper parameter E1-04. If speed command is above this value, actual d2-01 Limit 0.0 to 110.0...
Page 219
Table A.1 Parameter List (Continued) Parameter Name Parameter Setting Factory Menu Description LCD Digital Operator Range Setting Location Display V/F Pattern 155 to 255.0 240V Input Voltage Setting (240V) E1-01 Set to the nominal voltage of the incoming line. Quick Setting 310 to 510.0 Input Voltage 480V...
Page 220
Table A.1 Parameter List (Continued) Parameter Name Parameter Setting Factory Menu Description LCD Digital Operator Range Setting Location Display Motor Setup Motor Rated Current 10% to E2-01 Set to the motor nameplate full load amps. Quick Setting Motor Rated FLA 200% Dependent E2-03...
Page 221
Table A.1 Parameter List (Continued) Parameter Name Parameter Setting Factory Menu Description LCD Digital Operator Range Setting Location Display Digital Inputs 0: 3-wire control FWD/REV selection for 3-wire sequence 1: Local/Remote Sel Hand/Auto Selection - Closed = Hand, Open = Auto 2: Option/Inv Sel Selects source of speed command and sequence Closed = b1-01 &...
Page 222
Table A.1 Parameter List (Continued) Parameter Name Parameter Setting Factory Menu Description LCD Digital Operator Range Setting Location Display 12: Forward Jog Closed = drive runs forward at speed command entered into parameter d1-17 13: Reverse Jog Closed = drive runs in reverse at speed command entered into parameter d1-17 14: Fault Reset Closed = Resets the drive after the fault and the run...
Page 223
Table A.1 Parameter List (Continued) Parameter Name Parameter Setting Factory Menu Description LCD Digital Operator Range Setting Location Display Digital Inputs 1E: Ref Sample Hold Analog speed command is sampled then held at time of input closure. 20: External fault, Normally Open, Always Detected, Ramp To Stop 21: External fault, Normally Closed, Always Detected, Ramp To Stop...
Page 224
Table A.1 Parameter List (Continued) Parameter Name Parameter Setting Factory Menu Description LCD Digital Operator Range Setting Location Display Digital Outputs 0: During RUN 1 = Closed when a run command is input or the drive is outputting voltage. 1: Zero Speed = Closed when drive output frequency is less than Fmin (E1-09) 2: Fref/Fout Agree 1 = Closed when drive output speed equals the speed command within the...
Page 225
Table A.1 Parameter List (Continued) Parameter Parameter Name Setting Factory Menu Description Range Setting Location LCD Digital Operator Display Analog Inputs H3-02 Terminal A1 Gain Setting Sets the speed command when 10V is input, as a 0.0 to 100.0% Programming Terminal A1 Gain percentage of the maximum output frequency (E1-04).
Page 226
Table A.1 Parameter List (Continued Parameter Setting Factory Menu Parameter Name Description Range Setting Location LCD Digital Operator Display Analog Outputs Selects which monitor will be output on terminals FM and AC. 1: Frequency Ref (100% = max. output frequency) 2: Output Freq (100% = max.
Page 227
Table A.1 Parameter List (Continued Parameter Setting Factory Menu Parameter Name Description Range Setting Location LCD Digital Operator Display Analog Outputs H4-06 Terminal AM Bias Setting Sets terminal AM output voltage (in percent of 10V) –110.0 to 0.0% Programming Terminal AM Bias when selected monitor is at 0% output.
Page 228
Table A.1 Parameter List (Continued Parameter Setting Factory Menu Parameter Name Description Range Setting Location LCD Digital Operator Display Motor Overload Enables or disables the motor thermal overload protection. Motor Overload Protection 0: Disabled L1-01 Selection 0 to 1 Programming 1: Std Fan Cooled (Enabled) MOL Fault Select 2: Std Blower Cooled...
Page 229
Table A.1 Parameter List (Continued Parameter Setting Factory Menu Parameter Name Description Range Setting Location LCD Digital Operator Display Stall Prevention 0: Disabled (Motor accelerates at active acceleration, C1-01 or C1-03. The motor may stall if load is too heavy or accel time is too short). 1: General Purpose (When output current exceeds L3-02 Stall Prevention Selection During level, acceleration stops.
Page 230
Table A.1 Parameter List (Continued Parameter Setting Factory Menu Parameter Name Description Range Setting Location LCD Digital Operator Display Ref Detection Speed Agreement Detection Level L4-01 0.0 to 200.0 0.0Hz Programming L4-01 and L4-02 are used in conjunction with the Spd Agree Level multi-function outputs, (H2-01and H2-02) as a setpoint Speed Agreement Detection Width...
Page 231
Table A.1 Parameter List (Continued Parameter Setting Factory Menu Parameter Name Description Range Setting Location LCD Digital Operator Display Hdwe Protection Internal Dynamic Braking Resis- 0: Not Provided L8-01 tor Protection Selection 0 or 1 Programming 1: Provided DB Resistor Prot When the cooling fin temperature exceeds the value set Overheat Pre-Alarm Level 50 to 130...
Page 232
Table A.1 Parameter List (Continued Parameter Setting Factory Menu Parameter Name Description Range Setting Location LCD Digital Operator Display High Slip Sets how aggressively the drive decreases the output High-Slip Braking Deceleration frequency as it stops the motor. If overvoltage (OV) n3-01 Frequency Width 1 to 20...
Page 233
Table A.1 Parameter List (Continued Parameter Setting Factory Menu Parameter Name Description Range Setting Location LCD Digital Operator Display Sets unit display for the frequency reference parameters and frequency related monitors when o1-03 ≥ 40. 0: WC:InchOfWater 1: PSI:lb/SqrInch 2: GPM:Gallons/Min 3: F:DegFahrenheit Frequency Reference Display o1-09...
Page 234
Table A.1 Parameter List (Continued Parameter Setting Factory Menu Parameter Name Description Range Setting Location LCD Digital Operator Display Cumulative Cooling Fan o2-10 Operation Time Setting Sets the initial value of the heatsink fan operation time. 0 to 65535 0 hours Programming Fan ON Time Set Clears the fault memory contained in the U2 and U3...
Monitor List Table A.2 Monitor List (Continued) Parameter Parameter Name Description LCD Digital Operator Display DC Bus Voltage U1-07 Displays DC Bus Voltage DC Bus Voltage Output Power U1-08 Displays Drive output power Output kWatts Displays Drive input terminal status 0 0 0 0 0 0 0 1: FWD.
Page 236
Table A.2 Monitor List (Continued) Parameter Parameter Name Description LCD Digital Operator Display Motor Secondary Current (I Displays the amount of current being used by the motor to U1-18 Mot SEC Current produce torque (Iq). Output Frequency After Soft Start Displays the frequency reference (speed command) after the U1-20 SFS Output...
Fault Trace List Table A.3 Fault Trace List Fault Trace Current Fault U2-01 Current Fault Previous Fault U2-02 Last Fault Frequency Reference at Most Recent Fault U2-03 Frequency Ref Output Frequency at Most Recent Fault U2-04 Output Freq Output Current at Most Recent Fault U2-05 Output Current Output Voltage at Most Recent Fault...
Fault History List Table A.4 Fault History List Fault History Most Recent Fault U3-01 Last Fault Most Recent Fault U3-02 Fault Message 2 Most Recent Fault U3-03 Fault Message 3 Most Recent Fault U3-04 Fault Message 4 Cumulative Operation Time at Most Recent Fault U3-05 Elapsed Time 1 Cumulative Operation Time at 2...
Appendix B Capacity Related Parameters This appendix lists the parameters affected by the Drive Capacity setting of o2-04. Drive Capacity ................2 Parameters Affected by o2-04 ........... 3 Capacity Related Parameter Values........... 4 Capacity Related Parameters B - 1 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
Drive Capacity Parameter o2-04 sets the Drive capacity according to the model number. Parameter o2-04 will need to be adjusted when replacing a control board. If a Control PCB is changed, the first time the Drive is powered up, parameter o2-04 must be set to the appropriate value listed in Table B.1 for the Drive model number.
Page 242
Parameters Affected by o2-04 The factory setting of the following parameters may change when the Drive capacity is changed. Table B.2 Parameters Affected by o2-04 Parameter Name Parameter Number Digital Operator Display Energy Saving Coefficient Value b8-04 Energy Save COEF Carrier Frequency Selection C6-02 CarrierFreq Sel...
Page 243
Capacity Related Parameter Values The following tables detail the factory default settings for the parameters that are affected by the setting of parameter o2-04. Table B.3 208 VAC Drives Factory Factory Factory Factory Factory Factory Factory Factory Factory Factory Drive Model Nominal Default Default...
Appendix C Specifications This appendix details the standard Drive Specifications. Standard Drive and Bypass Specifications ........2 208 VAC ..................2 480 VAC ..................3 All Voltages ................4 Specifications C - 1 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
Standard Drive and Bypass Specifications The standard Drive and Bypass specifications are listed in the following tables. 208 VAC Table C.1 208 VAC Drive and Bypass Specifications Bypass Model Number E7L_ * D003 D004 D007 D010 D016 D024 D030 D046 D059 D074 Motor HP...
Page 248
480 VAC Table C.2 480 VAC Drive and Bypass Specifications Bypass Model Number E7L_ * B001 B002 B003 B004 B007 B011 B014 Motor HP (460V) 0.5/0.75 1.5/2 Bypass rated output current (A) Drive Model Number CIMR-E7U 42P2 42P2 42P2 42P2 43P7 45P5 47P5...
Page 249
All Voltages Table C.3 Common Drive Specifications All Models Specification Sine wave PWM Control method V/f control Speed range 40:1 ±2 to 3% (77 ° F ± 50 ° F) (25 ° C ± 10 ° C) Speed control accuracy Digital references: ±...
N2 , please refer to the Technical Manual (TM.E7.22). These ® two documents can be found on the CD-ROM included with this Drive and Bypass unit or at www.drives.com. E7N and Serial Communication ............2 Using Modbus Communication ............3 Modbus Communication Configuration ........3 Communication Specifications ........... 3 Communication Connection Terminal ........
E7N and Serial Communication The H/O/A selector keys must be in the AUTO position if serial communication is to be used for E7N run, stop or speed control. E7N serial communication may be used for any or all of the following monitoring and control functions:...
Using Modbus Communication Serial communication can be performed with Direct Digital Controllers (DDCs) or similar devices using the Modbus protocol. Modbus Communication Configuration Modbus communication is configured using 1 master (PLC) and a maximum of 31 slaves. Serial communication between master and slave is normally initiated by the master and responded to by the slaves.
RS-485 Switch DIP Switch S1-1 located on E7N terminal board. Terminating resistance (1/2W, 110 Ohms) Fig D.2 Communication Connection Terminals and Terminating Resistance 1. Separate the communication cables from the main circuit cables and control circuit wiring. 2. Use shielded cables for the communication cable, and use proper shield clamps.
Page 254
Related Parameters Table D.2 Serial Communication Related Parameters Parameter Setting Factory Chapter Menu Parameter Name Description Range Setting Ref # Location Digital Operator Display Selects the speed command (frequency reference) input source. Frequency Reference 0: Operator - Digital preset speed d1-01 Quick b1-01 Selection...
Page 255
Message Format In Modbus communication, the master sends commands to the slave, and the slave responds. The message format is configured for both sending and receiving as shown below. The length of the data packets is changed by the command (function) contents.
Page 256
Error Check Errors are detected during communication using CRC-16. Perform calculations using the following method: 1. The factory setting for CRC-16 communication is typically zero, but when using the Modbus system, set the factory setting to one (e.g., set all 16 bits to 1). 2.
Modbus Function Code Details Reading/Holding Register Contents (03H) Read the contents of the storage register only for specified quantities. The addresses must be consecutive, starting from a specified address. The data content of the storage register are separated into higher 8 bits and lower 8 bits. The following table shows message examples when reading status signals, error details, data link status, and frequency references from the slave 2 Drive.
Page 258
Loopback Test (08H) The loopback test returns the command message directly as the response message without changing the contents to check the communications between the master and slave. Set user-defined test code and data values. The following table shows a message example when performing a loopback test with the slave 1 Drive. Response Message Response Message Command Message...
Modbus Data Tables The data tables are shown below. The types of data are as follows: Reference data, monitor data and broadcast data. Reference Data The reference data table is shown below. Reference data can be read and written to. Table D.4 Reference Data Register No.
Page 260
Monitor Data The following table shows the monitor data. Monitor data can only be read. Table D.5 Monitor Data Register No. Contents Drive status Bit 0 Operation 1: Operating 0: Stopped Bit 1 Reverse operation 1: Reverse operation 0: Forward operation Bit 2 Drive startup complete 1: Completed 0: Not completed Bit 3...
Page 261
Table D.5 Monitor Data (Continued) Register No. Contents Sequence input status Bit 0 Input terminal S1 1: ON 0: OFF Bit 1 Input terminal S2 1: ON 0: OFF Bit 2 Multi-function digital input terminal S3 1: ON 0: OFF 002BH Bit 3 Multi-function digital input terminal S4 1: ON 0: OFF...
Page 262
Broadcast Data The following table shows the broadcast data. Broadcast data can be written to. Table D.6 Broadcast Data Register Contents Address Operation signal Bit 0 Run command 1: Operating 0: Stopped Bit 1 Reverse operation command 1: Reverse 0: Forward Bits 2 and 3 Not used Bit 4...
Page 263
Error Codes The following table shows Modbus communication error codes. Table D.8 Error Codes Error Contents Code Function code error A function code other than 03H, 08H, or 10H has been set by the PLC. Invalid register number error • The register address you are attempting to access is not recorded anywhere. •...
Modbus Self-Diagnosis The Drive has a built-in function for self-diagnosing the operations of serial communication interface circuits. The self-diagnosis function connects the communication parts of the send and receive terminals, receives the data sent by the Drive, and checks if communication is being performed normally. Perform the self-diagnosis function using the following procedure.
Metasys N2 Point Database Metasys N2 Analog Input (AI) Summary Table D.9 Metasys N2 Analog Input Summary (E7 to Metasys N2) Object ID Object Name Units E7 Parameter AI 1 SPEED REFERENCE 0.01 Hz U1-01 AI 2 OUTPUT SPEED 0.01 Hz U1-02 AI 3 OUTPUT CURRENT...
Page 266
Metasys N2 Analog Output (AO) Summary Table D.10 Metasys N2 Analog Output Summary (Metasys N2 to E7) Object ID Object Name Units Default Value E7 Parameter AO 1 SPEED COMMAND 0.01 Hz AO 2 ACCELERATION TIME 30.0 C1-01 AO 3 DECELERATION TIME 30.0 C1-02...
Metasys N2 Binary Input (BI) Summary Table D.11 Metasys N2 Binary Input Summary (E7 to Metasys N2) Object ID Object Name Default Off (0) State On (1) State BI 1 RUN / STOP MONITOR STOPPED RUNNING BI 2 FORWARD / REVERSE MONITOR FORWARD REVERSE BI 3...
Mailbox Function Points Reading a Drive Parameter Two points are defined for reading any Drive parameter: AO 30 Specifies the parameter to be read from the E7 Drive AI 38 Reports the value of the parameter specified in AO 30 When this point is read, it retrieves data from the parameter and sends it to the controller Example: Writing a value of 387 (183 hex) to AO 30 specifies Drive parameter b1-04.
APOGEE FLN Point Database APOGEE FLN Point List Summary This database is for APOGEE FLN Application 2721 and features 97 logical points: 29 Logical Analog Inputs (LAI), 35 Log- ical Analog Outputs (LAO), 19 Logical Digital Inputs (LDI) and 14 Logical Digital Outputs (LDO). These points configure, control or monitor the operation of the Drive.
Page 270
Table D.13 APOGEE FLN Application 2721 Point Number Summary (Continued) Point Point Factory Default Engr. Units Slope Intercept Drive Point Name Number Type (SI Units) (SI Units) (SI Units) (SI Units) Text Text Parameter FREQ LOW LIM – – d2-02 {40} MULTI OUT 1 –...
Page 271
Table D.13 APOGEE FLN Application 2721 Point Number Summary (Continued) Point Point Factory Default Engr. Units Slope Intercept Drive Point Name Number Type (SI Units) (SI Units) (SI Units) (SI Units) Text Text Parameter {87} PID OUT CAP 0.01 – –...
APOGEE FLN Logical Digital Input (LDI) Summary Table D.16 APOGEE FLN Application 2721 Logical Digital Input (LDI) Summary (E7 to APOGEE FLN) Point Defaul Off (0) On (1) Database Descriptor Slope Intercept Number State State Parameter MINOR FLT NO FLT FAULT U1-12 (Bit 6) MAJOR FLT...
Mailbox Function Points Reading a Drive Parameter Two points are defined for reading any Drive parameter: Specifies the parameter to be read from Reports the value of the parameter specified in Point #70 When this point is read, it retrieves data from the parameter and sends it to the controller Example: Entering a value of 387 (183 hex) in Point #70 specifies Drive parameter B1-04.
Appendix E Peripheral Devices This appendix describes recommended branch short circuit protection and peripheral devices. Branch Circuit Short Circuit Protection....... E-2 Branch Circuit Overload Protection........E-3 Peripheral Devices ............. E-4 Peripheral Devices E - 1 Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
Page 277
Branch Circuit Short Circuit Protection The following peripheral devices may be required between the AC main circuit power supply and the Drive input terminals L1(R), L2(S), and L3(T). Refer to applicable codes to determine the devices necessary for a given installation.
AC and DC reactor When using the E7N on a power supply transformer with a capacity of 600kVA or more, install a DC reactor. The reactor improves the input power factor and provides protection to the rectifier circuit within the Drive.
Page 280
Contact Drives Technical Support for help with any of these needs. Technical Training Training is conducted at Yaskawa training centers, at customer sites, and via the internet. For information, visit www.yaskawa.com or call 1-800-YASKAWA (927-5292). From the phone menu, dial 2 for Inverter and Drive Products, then 4 for Product Training.
Page 281
Phone: (800) YASKAWA (800-927-5292) or 1-847-887-7000 Fax: (847) 887-7370 Internet: http://www.yaskawa.com YEA Document Number: TM.E7N.01 03/01/2009 Rev. 09-03 Data subject to change without notice. Yaskawa Electric America, Inc. Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
Need help?
Do you have a question about the E7N and is the answer not in the manual?
Questions and answers