Settings - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

1MRK 511 287-UUS A
6.2.5
Table 32:
OC4PTOC (51_67) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
DirMode1
Disabled
Non-directional
Forward
Reverse
Characterist1
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
RI type
RD type
I1>
5 - 2500
t1
0.000 - 60.000
k1
0.05 - 999.00
IMin1
5 - 10000
Table continues on next page
Technical manual
Name
Type
TR4
BOOLEAN
START
BOOLEAN
ST1
BOOLEAN
ST2
BOOLEAN
ST3
BOOLEAN
ST4
BOOLEAN
STL1
BOOLEAN
STL2
BOOLEAN
STL3
BOOLEAN
ST2NDHRM
BOOLEAN

Settings

Unit
Step
-
-
-
-
-
-
%IB
1
s
0.001
-
0.01
%IB
1
Description
Trip signal from step 4
General pickup signal
Pick up signal from step 1
Pick up signal from step 2
Pickup signal step 3
Pickup signal step 4
Pickup signal from phase A
Pickup signal from phase B
Pickup signal from phase C
Second harmonic detected
Default
Description
Disabled
Disable/Enable Operation
Non-directional
Directional mode of step 1 off / non-directional /
forward / reverse
ANSI Def. Time
Selection of time delay curve type for step 1
1000
Phase current operate level for step1 in % of
IBase
0.000
Definite time delay of step 1
0.05
Time multiplier for the inverse time delay for
step 1
100
Minimum operate current for step1in% of IBase
Section 6
Current protection