Settings - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

Section 10
Control
10.3.6.5
Table 190:
LOCREM Non group settings (basic)
Name
Values (Range)
ControlMode
Internal LR-switch
External LR-switch
10.3.7
10.3.7.1
10.3.7.2
258
Table 189:
LOCREM Output signals
Name
Type
OFF
BOOLEAN
LOCAL
BOOLEAN
REMOTE
BOOLEAN
VALID
BOOLEAN

Settings

Unit
Step
-
-
Local remote control LOCREMCTRL
Identification
Function description
Local remote control
Functionality
The signals from the local HMI or from an external local/remote switch are applied via the
function blocks LOCREM and LOCREMCTRL to the Bay control QCBAY function
block. A parameter in function block LOCREM is set to choose if the switch signals are
coming from the local HMI or from an external hardware switch connected via binary
inputs.
Description
Control is disabled
Local control is activated
Remote control is activated
Outputs are valid
Default
Description
Internal LR-switch
Control mode for internal/external LR-switch
IEC 61850
IEC 60617
identification
identification
LOCREMCTRL
-
1MRK 511 287-UUS A
ANSI/IEEE C37.2
device number
-
Technical manual