ABB REC650 ANSI Technical Manual page 396

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

Section 11
Logic
Table 302:
TIMERSETQT Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
t
0.000 - 90000.000
11.3.2.7
390
Signals
Table 300:
TIMERSETQT Input signals
Name
Type
INPUT
BOOLEAN
Table 301:
TIMERSETQT Output signals
Name
Type
ON
BOOLEAN
OFF
BOOLEAN
Settings
Unit
Step
-
-
s
0.001
ANDQT function block
Identification
Function description
ANDQT function block
Functionality
ANDQT function is used to form general combinatory expressions with boolean
variables. ANDQT function block has four inputs and two outputs.
Default value on all four inputs are logical 1 which makes it possible for the user to just
use the required number of inputs and leave the rest un-connected. The output OUT has
a default value 0 initially, which will suppress one cycle pulse if the function has been put
in the wrong execution order.
Default
Description
0
Input signal
Description
Output signal, pick-up delayed
Output signal, drop-out delayed
Default
Description
Disabled
Operation Disabled/Enabled
0.000
Delay for settable timer n
IEC 61850
IEC 60617
identification
identification
ANDQT
1MRK 511 287-UUS A
ANSI/IEEE C37.2
device number
-
-
Technical manual