1MRK 511 287-UUS A
10.3.4.5
Table 184:
SXSWI Non group settings (basic)
Name
Values (Range)
tStartMove
0.000 - 60.000
tIntermediate
0.000 - 60.000
AdaptivePulse
Not adaptive
Adaptive
tOpenPulse
0.000 - 60.000
tClosePulse
0.000 - 60.000
SwitchType
Load Break
Disconnector
Grounding Switch
HS Groundg.
Switch
SuppressMidPos
Disabled
Enabled
10.3.5
10.3.5.1
Technical manual
Name
Type
UPD_BLKD
BOOLEAN
POSITION
INTEGER
OPENPOS
BOOLEAN
CLOSEPOS
BOOLEAN
TR_POS
INTEGER
CNT_VAL
INTEGER
L_CAUSE
INTEGER

Settings

Unit
Step
s
0.001
s
0.001
-
-
s
0.001
s
0.001
-
-
-
-
Bay control QCBAY
Identification
Function description
Bay control
Description
Update of position indication is blocked
Apparatus position indication
Apparatus open position
Apparatus closed position
Truck position indication
Operation counter value
Latest value of the error indication during command
Default
Description
3.000
Supervision time for the apparatus to move
after a command
15.000
Allowed time for intermediate position
Not adaptive
Output resets when a new correct end position
is reached
0.200
Output pulse length for open command
0.200
Output pulse length for close command
Disconnector
1=LoadBreak,2=Disconnector,3=GroundSw,
4=HighSpeedGroundSw
Enabled
Mid-position is suppressed during the time
tIntermediate
IEC 61850
IEC 60617
identification
identification
QCBAY
-
Section 10
Control
ANSI/IEEE C37.2
device number
-
255