1MRK 511 287-UUS A
EXE_CL
OPENPOS
CLOSEPOS
tStartMove timer
tIntermediate timer
IEC05000097 V1 EN
Figure 125:
The timers tStartMove and tIntermediate
Technical manual
Close pulse duration
t1
tStartMove
The timers tOpenPulse and tClosePulse are the length of the execute output pulses to be
sent to the primary equipment. Note that the output pulses for open and close command
can have different pulse lengths. The pulses can also be set to be adaptive with the
configuration parameter AdaptivePulse. Figure
output pulse. The AdaptivePulse parameter will have affect on both execute output pulses.
OPENPOS
CLOSEPOS
EXE_CL
EXE_CL
IEC05000098 V1 EN
Figure 126:
Execute output pulse
t2
tIntermediate
126
tClosePulse
tClosePulse
Section 10
AdaptivePulse = TRUE
if t1 > tStartMove then
"switch-not-start-moving"
attribute in 'cause' is set
if t2 > tIntermediate then
"persisting-intermediate-state"
attribute in 'cause' is set
en05000097.vsd
shows the principle of the execute
AdaptivePulse=FALSE
AdaptivePulse=TRUE
en05000098.vsd
Control
273