Section 11
Logic
416
tOverflow
tWarning
tAlarm
BLOCK
RESET
IN
IEC12000195 V2 EN
Figure 196:
TEIGGIO Simplified logic
TEIGGIO main functionalities are
integrate the elapsed time when IN has been high
applicable to long time integration (≤999 999.9 seconds)
output ACCTIME presents integrated value in seconds to all tools
integrated value is retained in non-volatile memory, if any warning, alarm or
overflow occurs
any retained value with a warning/alarm/overflow shall be available as the
initiation value for the integration followed by a restart.
RESET: Reset the integration value. Consequently all other outputs are also reset
unconditionally on the input IN value
reset the value of the non-volatile memory to zero.
BLOCK: Freeze the integration and block/reset the other outputs
unconditionally on the signal value
BLOCK request overrides RESET request.
Monitor and report the conditions of limit transgression
overflow if output ACCTIME > tOverflow
alarm if ACCTIME > tAlarm
warning if ACCTIME > tWarning.
The ACCTIME output represents the integrated time in seconds while tOverflow, tAlarm
and tWarning are the time limit parameters in seconds.
Loop Delay
Transgression Supervision
Time Integration
Loop Delay
1MRK 511 287-UUS A
OVERFLOW
WARNING
Plus Retain
IEC12000195-2-en.vsd
Technical manual
ALARM
ACCTIME