Signals; Settings; Function Block - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

1MRK 511 287-UUS A
9.3.3
9.3.4
9.3.5
Table 163:
TCSSCBR Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
tDelay
0.020 - 300.000
9.3.6
Technical manual

Function block

GUID-6F85BD70-4D18-4A00-A410-313233025F3A V2 EN
Figure 94:
Function block

Signals

Table 161:
TCSSCBR Input signals
Name
Type
TCS_STATE
BOOLEAN
BLOCK
BOOLEAN
Table 162:
TCSSCBR Output signals
Name
Type
ALARM
BOOLEAN

Settings

Unit
Step
-
-
s
0.001
Operation principle
The function can be enabled and disabled with the Operation setting. The corresponding
parameter values are Enable and Disable.
The operation of trip circuit supervision can be described by using a module diagram. All
the modules in the diagram are explained in the next sections.
Secondary system supervision
Default
Description
0
Trip circuit fail indication from I/O-card
0
Block of function
Description
Trip circuit fault indication
Default
Description
Enabled
Operation Disabled/Enabled
3.000
Operate time delay
Section 9
219