Operation Principle - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

1MRK 511 287-UUS A
Name
Values (Range)
CBReadyType
CO
OCO
t2 3Ph
0.00 - 6000.00
t3 3Ph
0.00 - 6000.00
t4 3Ph
0.00 - 6000.00
t5 3Ph
0.00 - 6000.00
tInhibit
0.000 - 60.000
Follow CB
Disabled
Enabled
AutoCont
Disabled
Enabled
tAutoContWait
0.000 - 60.000
UnsucClByCBChk
NoCBCheck
CB check
BlockByUnsucCl
Disabled
Enabled
ZoneSeqCoord
Disabled
Enabled
10.2.6
10.2.6.1
Technical manual
Unit
Step
-
-
s
0.01
s
0.01
s
0.01
s
0.01
s
0.001
-
-
-
-
s
0.001
-
-
-
-
-
-

Operation principle

Initiate auto-reclosing and conditions for initiation of a reclosing cycle
The usual way in which to initiate a reclosing cycle, or sequence, is to initiate it when a line
protection tripping has occurred, by applying a signal to the RI input.
For a new auto-reclosing cycle to be started, a number of conditions need to be met. They
are linked to dedicated inputs. The inputs are:
CBREADY: CB ready for a reclosing cycle, for example, charged operating gear
52a: to ensure that the CB was closed when the line fault occurred and initiation was
applied
No blocking or inhibit signal shall be present.
After the initiate has been accepted, it is latched in and an internal signal "Started" is set.
It can be interrupted by certain events, like an inhibit signal.
To initiate auto-reclosing by CB position Open instead of from protection trip signals, one
has to configure the CB Open position signal to inputs 52a and RI and set a parameter
StartByCBOpen = Enabled and CBAuxContType = NormClosed (normally closed, 52b).
Default
Description
CO
Select type of circuit breaker ready signal
CO/OCO
30.00
Open time for shot 2, three-phase
30.00
Open time for shot 3, three-phase
30.00
Open time for shot 4, three-phase
30.00
Open time for shot 5, three-phase
5.000
Inhibit reclosing reset time
Disabled
Advance to next shot if CB has been closed
during dead time
Disabled
Continue with next reclosing-shot if breaker did
not close
2.000
Wait time after close command before
proceeding to next shot
NoCBCheck
Unsuccessful closing signal obtained by
checking CB position
Disabled
Block AR at unsuccessful reclosing
Disabled
Coordination of down stream devices to local
protection unit's AR
Section 10
Control
241