Technical Data; Unsymmetrical Current Detection - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

1MRK 511 287-UUS A
6.9.7.2
6.9.8
6.10
6.10.1
Technical manual

Unsymmetrical current detection

Unsymmetrical current indicated if:
any phase current is lower than CurrUnsymPU of the highest current in the three
phases.
the highest phase current is greater than CurrRelPU of IBase.
If these conditions are true, an unsymmetrical condition is detected. This detection is
enabled to generate a trip after a set time delay tTrip if the detection occurs in the next 200
ms after the circuit breaker has received a command to open trip or close and if the
unbalance persists. The 200 ms limitation is for avoiding unwanted operation during
unsymmetrical load conditions.
The pole discrepancy protection is informed that a trip or close command has been given
to the circuit breaker through the inputs CLOSECMD (for closing command information)
and OPENCMD (for opening command information). These inputs can be connected to
terminal binary inputs if the information are generated from the field (that is from
auxiliary contacts of the close and open push buttons) or may be software connected to the
outputs of other integrated functions (that is close command from a control function or a
general trip from integrated protections).

Technical data

Table 84:
CCRPLD (52PD) technical data
Function
Operate value, current
asymmetry level
Reset ratio
Time delay
Broken conductor check BRCPTOC (46)
Identification
Function description
Broken conductor check
Range or value
(0-100) %
>95%
(0.000-60.000) s
IEC 61850
IEC 60617
identification
identification
BRCPTOC
-
Section 6
Current protection
Accuracy
± 1.0% of I
n
-
± 0.5% ± 25 ms
ANSI/IEEE C37.2
device number
46
149

Advertisement

Table of Contents
loading

Table of Contents