Section 12
Monitoring
12.14.5
Table 408:
LMBRFLO Group settings (basic)
Name
Values (Range)
R1A
0.001 - 1500.000
X1A
0.001 - 1500.000
R1B
0.001 - 1500.000
X1B
0.001 - 1500.000
R1L
0.001 - 1500.000
X1L
0.001 - 1500.000
R0L
0.001 - 1500.000
X0L
0.001 - 1500.000
R0M
0.000 - 1500.000
X0M
0.000 - 1500.000
LineLengthUnit
kilometer
miles
LineLength
0.0 - 10000.0
Table 409:
LMBRFLO Non group settings (basic)
Name
Values (Range)
DrepChNoI_A
1 - 30
DrepChNoI_B
1 - 30
DrepChNoI_C
1 - 30
DrepChNoIN
0 - 30
DrepChNoIP
0 - 30
Table continues on next page
508
Name
Type
BCD_8
BOOLEAN
BCD_4
BOOLEAN
BCD_2
BOOLEAN
BCD_1
BOOLEAN

Settings

Unit
Step
ohm/p
0.001
ohm/p
0.001
ohm/p
0.001
ohm/p
0.001
ohm/p
0.001
ohm/p
0.001
ohm/p
0.001
ohm/p
0.001
ohm/p
0.001
ohm/p
0.001
-
-
-
0.1
Unit
Step
Ch
1
Ch
1
Ch
1
Ch
1
Ch
1
Description
Distance in binary coded data, bit represents 8%
Distance in binary coded data, bit represents 4%
Distance in binary coded data, bit represents 2%
Distance in binary coded data, bit represents 1%
Default
Description
2.000
Source resistance A (near end)
12.000
Source reactance A (near end)
2.000
Source resistance B (far end)
12.000
Source reactance B (far end)
2.000
Positive sequence line resistance
12.500
Positive sequence line reactance
8.750
Zero sequence line resistance
50.000
Zero sequence line reactance
0.000
Zero sequence mutual resistance
0.000
Zero sequence mutual reactance
kilometer
Line length unit
40.0
Length of line
Default
Description
1
Recorder Input number recording phase
current, IA
2
Recorder Input number recording phase
current, IB
3
Recorder Input number recording phase
current, IC
4
Recorder input number recording residual
current, IN
0
Recorder input number recording 3I0 on
parallel line
1MRK 511 287-UUS A