Section 11
Logic
Table 297:
PULSETIMERQT Non group settings (basic)
Name
Values (Range)
t
0.000 - 90000.000
11.3.2.5
388
Settings
Unit
Step
s
0.001
XORQT function block
Identification
Function description
XORQT function block
Functionality
The exclusive OR function (XORQT) function is used to generate combinatory
expressions with boolean variables. XORQT function has two inputs and two outputs.
One of the outputs is inverted. The output signal is 1 if the input signals are different and
0 if they are equal.
Function block
XORQT
INPUT1
OUT
INPUT2
NOUT
IEC09000300-1-en.vsd
IEC09000300 V1 EN
Figure 181:
XORQT function block
Signals
Table 298:
XORQT Input signals
Name
Type
INPUT1
BOOLEAN
INPUT2
BOOLEAN
Table 299:
XORQT Output signals
Name
Type
OUT
BOOLEAN
NOUT
BOOLEAN
Default
Description
0.010
Pulse time length
IEC 61850
IEC 60617
identification
identification
XORQT
Default
Description
0
Input signal 1
0
Input signal 2
Description
Output signal
Inverted output signal
1MRK 511 287-UUS A
ANSI/IEEE C37.2
device number
-
-
Technical manual