Function Block - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

1MRK 511 287-UUS A
12.13.3
12.13.4
12.13.5
12.13.6
Technical manual

Function block

MVEXP
RANGE*
HIGHHIGH
HIGH
NORMAL
LOW
LOWLOW
IEC09000215-1-en.vsd
IEC09000215 V1 EN
Figure 222:
MVEXP function block
Signals
Table 403:
MVEXP Input signals
Name
Type
RANGE
INTEGER
Table 404:
MVEXP Output signals
Name
Type
HIGHHIGH
BOOLEAN
HIGH
BOOLEAN
NORMAL
BOOLEAN
LOW
BOOLEAN
LOWLOW
BOOLEAN
Settings
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).
GlobalBaseSel: Selects the global base value group used by the function to define (IBase),
(VBase) and (SBase).
Operation principle
The input signal must be connected to a range output of a measuring function block
(CVMMXN, CMMXU, VMMXU, VNMMXU, CMSQI, VMSQ or MVGGIO). The
function block converts the input integer value to five binary output signals according to
table
405.
Default
Description
0
Measured value range
Description
Measured value is above high-high limit
Measured value is between high and high-high limit
Measured value is between high and low limit
Measured value is between low and low-low limit
Measured value is below low-low limit
Section 12
Monitoring