Settings - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

1MRK 511 287-UUS A
6.11.2.4
Table 93:
GOPPDOP (32) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OpMode1
Disabled
OverPower
Power1
0.0 - 500.0
Angle1
-180.0 - 180.0
TripDelay1
0.010 - 6000.000
OpMode2
Disabled
OverPower
Power2
0.0 - 500.0
Angle2
-180.0 - 180.0
TripDelay2
0.010 - 6000.000
Table 94:
GOPPDOP (32) Group settings (advanced)
Name
Values (Range)
k
0.00 - 0.99
Table 95:
GOPPDOP (32) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
Mode
A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
Technical manual

Settings

Unit
Step
-
-
-
-
%
0.1
Deg
0.1
s
0.001
-
-
%
0.1
Deg
0.1
s
0.001
Unit
Step
-
0.01
Unit
Step
-
1
-
-
Default
Description
Disabled
Operation Disable / Enable
OverPower
Operation mode 1
1.0
Power setting for stage 1 in % of calculated
power base value
0.0
Characteristic angle for stage 1
1.000
Trip delay for stage 1
OverPower
Operation mode 2
1.0
Power setting for stage 2 in % of calculated
power base value
0.0
Characteristic angle for stage 2
1.000
Trip delay for stage 2
Default
Description
0.00
Low pass filter coefficient for power
measurement, V and I
Default
Description
1
Selection of one of the Global Base Value
groups
Pos Seq
Mode of measurement for current and voltage
Section 6
Current protection
155

Advertisement

Table of Contents
loading