Time Synchronization - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

Section 15
Basic IED functions
15.2
15.2.1
15.2.2
15.2.2.1
15.2.2.2
Table 491:
TIMESYNCHGEN Non group settings (basic)
Name
Values (Range)
CoarseSyncSrc
Disabled
SNTP
DNP
IEC60870-5-103
FineSyncSource
Disabled
SNTP
IRIG-B
SyncMaster
Disabled
SNTP-Server
590

Time synchronization

Functionality
The time synchronization source selector is used to select a common source of absolute
time for the IED when it is a part of a control and a protection system. This makes it
possible to compare event and disturbance data between all IEDs in a station automation
system.
Micro SCADA OPC server should not be used as a time synchronization
source.
Time synchronization TIMESYNCHGEN
Identification
Function description
Time synchronization
Settings
Unit
Step
-
-
-
-
-
-
IEC 61850
IEC 60617
identification
identification
TIMESYNCHGE
-
N
Default
Description
Disabled
Coarse time synchronization source
Disabled
Fine time synchronization source
Disabled
Activate IED as synchronization master
1MRK 511 287-UUS A
ANSI/IEEE C37.2
device number
-
Technical manual