Functionality - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

1MRK 511 287-UUS A
14.7
14.7.1
14.7.2
14.7.3
14.7.4
Technical manual
GOOSE function block to receive a measurand value
GOOSEMVRCV
Identification
Function description
GOOSE function block to receive a
measurand value

Functionality

GOOSEMVRCV is used to receive measured value using IEC61850 protocol via
GOOSE.
Function block
GOOSEMVRCV
BLOCK
^MVOUT
DATAVALID
COMMVALID
TEST
IEC10000251-1-en.vsd
IEC10000251 V1 EN
Figure 258:
GOOSEMVRCV function block
Signals
Table 474:
GOOSEMVRCV Input signals
Name
Type
BLOCK
BOOLEAN
Table 475:
GOOSEMVRCV Output signals
Name
Type
MVOUT
REAL
DATAVALID
BOOLEAN
COMMVALID
BOOLEAN
TEST
BOOLEAN
Station communication
IEC 61850
IEC 60617
identification
identification
GOOSEMVRCV
-
Default
Description
0
Block of function
Description
Measurand value output
Data valid for measurand value output
Communication valid for measurand value output
Test output
Section 14
ANSI/IEEE C37.2
device number
-
573

Advertisement

Table of Contents
loading