Monitored Data - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

Section 12
Monitoring
12.18.6
12.18.7
528

Monitored data

Table 430:
SSCBR Monitored data
Name
Type
CBOTRVT
REAL
CBCLTRVT
REAL
SPRCHRT
REAL
NO_OPR
INTEGER
NOOPRDAY
INTEGER
CBLIFE_A
INTEGER
CBLIFE_B
INTEGER
CBLIFE_C
INTEGER
IACC_A
REAL
IACC_B
REAL
IACC_C
REAL
Operation principle
The circuit breaker condition monitoring function includes a number of metering and
monitoring subfunctions. The functions can be enabled and disabled with the Operation
setting. The corresponding parameter values are Enable and Disable. The operation
counters are cleared when Operation is set to Disabled.
The operation of the functions can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
Values (Range)
Unit
-
ms
-
ms
-
s
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1MRK 511 287-UUS A
Description
Travel time of the CB during
opening operation
Travel time of the CB during
closing operation
The charging time of the CB
spring
Number of CB operation cycle
The number of days CB has
been inactive
CB Remaining life phase A
CB Remaining life phase B
CB Remaining life phase C
Accumulated currents power
(Iyt), phase A
Accumulated currents power
(Iyt), phase B
Accumulated currents power
(Iyt), phase C
Technical manual