The Bay control QCBAY function is used together with Local remote and local remote
control functions to handle the selection of the operator place per bay. QCBAY also
provides blocking functions that can be distributed to different apparatuses within the bay.
Function block
QCBAY
LR_OFF
PSTO
LR_LOC
UPD_BLKD
LR_REM
CMD_BLKD
LR_VALID
LOC
BL_UPD
REM
BL_CMD
IEC09000080_1_en.vsd
IEC09000080 V1 EN
Figure 112:
QCBAY function block
Signals
Table 185:
QCBAY Input signals
Name
Type
LR_OFF
BOOLEAN
LR_LOC
BOOLEAN
LR_REM
BOOLEAN
LR_VALID
BOOLEAN
BL_UPD
BOOLEAN
BL_CMD
BOOLEAN
Table 186:
QCBAY Output signals
Name
Type
PSTO
INTEGER
UPD_BLKD
BOOLEAN
CMD_BLKD
BOOLEAN
LOC
BOOLEAN
REM
BOOLEAN
Default
Description
0
External Local/Remote switch is in Off position
0
External Local/Remote switch is in Local position
0
External Local/Remote switch is in Remote position
0
Data representing the L/R switch position is valid
0
Steady signal to block the position updates
0
Steady signal to block the command
Description
Value for the operator place allocation
Update of position is blocked
Function is blocked for commands
Local operation allowed
Remote operation allowed
1MRK 511 287-UUS A
Technical manual