Section 12
Monitoring
12.18.7.2
530
breaker status monitoring can be described using a module diagram. All the modules in the
diagram are explained in the next sections.
POSCLOSE
POSOPEN
I_A
I_B
I3P
I_C
GUID-60ADC120-4B5A-40D8-B1C5-475E4634214B-ANSI V1 EN
Figure 232:
Functional module diagram for monitoring circuit breaker status BLOCK
and BLK_ALM inputs
Phase current check
This module compares the three phase currents with the setting AccDisLevel. If the current
in a phase exceeds the set level, information about phase is reported to the contact position
indicator module.
Contact position indicator
The circuit breaker status is open if the auxiliary input contact POSCLOSE is low, the
POSOPEN input is high and the current is zero. The circuit breaker is closed when the
POSOPEN input is low and the POSCLOSE input is high. The breaker is in the
intermediate position if both the auxiliary contacts have the same value, that is, both are
in the logical level "0" or "1", or if the auxiliary input contact POSCLOSE is low and the
POSOPEN input is high, but the current is not zero.
The status of the breaker is indicated with the binary outputs CBOPEN, CBINVPOS and
52a for open, error state and closed position respectively.
Circuit breaker operation monitoring
The purpose of the circuit breaker operation monitoring subfunction is to indicate if the
circuit breaker has not been operated for a long time.
The operation of the circuit breaker operation monitoring can be described by using a
module diagram. All the modules in the diagram are explained in the next sections.
Contact
position
indicator
Phase
current
check
1MRK 511 287-UUS A
CBOPEN
CBINVPOS
52a
Technical manual