Technical Data - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

1MRK 511 287-UUS A
12.14.8
12.15
12.15.1
Technical manual
= ×
×
+
×
V
p Z
I
R I
A
1L
A
F
A
EQUATION1603 V1 EN
Where:
I
is according to table 411.
A
The accuracy of the distance-to-fault calculation, using the non-compensated impedance
model, is influenced by the pre-fault load current. So, this method is only used if the load
compensated models do not function.

Technical data

Table 412:
LMBRFLO technical data
Function
Reactive and resistive reach
Phase selection
Maximum number of fault
locations
Station battery supervision SPVNZBAT
Identification
Function description
Station battery supervision function
Value or range
(0.001-1500.000) Ω/phase
According to input signals
100
IEC 61850
IEC 60617
identification
identification
SPVNZBAT
U<>
Section 12
Monitoring
(Equation 74)
Accuracy
± 2.0% static accuracy
± 2.0% degrees static angular
accuracy
Conditions:
Voltage range: (0.1-1.1) x V
n
Current range: (0.5-30) x I
n
-
-
ANSI/IEEE C37.2
device number
-
515