Function Block - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

Section 14
Station communication
14.5.3
14.5.4
14.5.5
Table 470:
GOOSEDPRCV Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
14.5.6
570

Function block

GOOSEDPRCV
BLOCK
^DPOUT
DATAVALID
COMMVALID
TEST
IEC10000249-1-en.vsd
IEC10000249 V1 EN
Figure 256:
GOOSEDPRCV function block
Signals
Table 468:
GOOSEDPRCV Input signals
Name
Type
BLOCK
BOOLEAN
Table 469:
GOOSEDPRCV Output signals
Name
Type
DPOUT
INTEGER
DATAVALID
BOOLEAN
COMMVALID
BOOLEAN
TEST
BOOLEAN
Settings
Unit
Step
-
-
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
Default
Description
0
Block of function
Description
Double point output
Data valid for double point output
Communication valid for double point output
Test output
Default
Description
Disabled
Operation Enable/Disable
1MRK 511 287-UUS A
Technical manual