Settings - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

1MRK 511 287-UUS A
10.3.5.5
Table 187:
QCBAY Non group settings (basic)
Name
Values (Range)
AllPSTOValid
Priority
No priority
10.3.6
10.3.6.1
10.3.6.2
10.3.6.3
10.3.6.4
Technical manual

Settings

Unit
Step
-
-
Local remote LOCREM
Identification
Function description
Local remote
Functionality
The signals from the local HMI or from an external local/remote switch are applied via the
function blocks LOCREM and LOCREMCTRL to the Bay control QCBAY function
block. A parameter in function block LOCREM is set to choose if the switch signals are
coming from the local HMI or from an external hardware switch connected via binary
inputs.
Function block
LOCREM
CTRLOFF
OFF
LOCCTRL
LOCAL
REMCTRL
REMOTE
LHMICTRL
VALID
IEC09000076_1_en.vsd
IEC09000076 V1 EN
Figure 113:
LOCREM function block
Signals
Table 188:
LOCREM Input signals
Name
Type
CTRLOFF
BOOLEAN
LOCCTRL
BOOLEAN
REMCTRL
BOOLEAN
LHMICTRL
INTEGER
Default
Description
Priority
Priority of originators
IEC 61850
IEC 60617
identification
identification
LOCREM
-
Default
Description
0
Disable control
0
Local in control
0
Remote in control
0
LHMI control
Section 10
Control
ANSI/IEEE C37.2
device number
-
257