Function block
ANDQT
INPUT1
OUT
INPUT2
NOUT
INPUT3
INPUT4
IEC09000297-1-en.vsd
IEC09000297 V1 EN
Figure 184:
ANDQT function block
Signals
Table 303:
ANDQT Input signals
Name
Type
INPUT1
BOOLEAN
INPUT2
BOOLEAN
INPUT3
BOOLEAN
INPUT4
BOOLEAN
Table 304:
ANDQT Output signals
Name
Type
OUT
BOOLEAN
NOUT
BOOLEAN
Settings
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).
Set-reset function block SRMEMORYQT
Identification
Function description
Set/reset logic component
Functionality
The Set-reset function (SRMEMORYQT) is a flip-flop with memory that can set or reset
an output from two inputs respectively. Each SRMEMORYQT function block has two
Default
Description
1
Input signal 1
1
Input signal 2
1
Input signal 3
1
Input signal 4
Description
Output signal
Inverted output signal
IEC 61850
IEC 60617
identification
identification
SRMEMORYQT
Section 11
Logic
ANSI/IEEE C37.2
device number
-
-
391