Section 12
Monitoring
12.22.2
12.22.3
12.22.4
Table 439:
I103EF Non group settings (basic)
Name
Values (Range)
FunctionType
1 - 255
12.23
12.23.1
544

Function block

I103EF
BLOCK
51_EFFW
52_EFREV
IEC10000290-1-en.vsd
IEC10000290 V1 EN
Figure 245:
I103EF function block
Signals
Table 438:
I103EF Input signals
Name
Type
BLOCK
BOOLEAN
51_EFFW
BOOLEAN
52_EFREV
BOOLEAN
Settings
Unit
Step
-
1
Function status fault protection for IEC 60870-5-103
I103FLTPROT
Functionality
I103FLTPROT is used for fault indications in monitor direction. Each input on the
function block is specific for a certain fault type and therefore must be connected to a
correspondent signal present in the configuration. For example: 68_TRGEN represents
the General Trip of the device, and therefore must be connected to the general trip signal
SMPPTRC_TRIP or equivalent.
The delay observed in the protocol is the time difference in between the signal that is
triggering the Disturbance Recorder and the respective configured signal to the IEC
60870-5-103 I103FLTPROT.
Default
Description
0
Block of status reporting
0
Information number 51, ground-fault forward
0
Information number 52, ground-fault reverse
Default
Description
160
Function type (1-255)
1MRK 511 287-UUS A
Technical manual