Function Block - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

Section 10
Control
10.7.3
10.7.4
10.7.5
10.7.6
352

Function block

DPGGIO
OPEN
POSITION
CLOSE
VALID
IEC09000075_1_en.vsd
IEC09000075 V1 EN
Figure 155:
DPGGIO function block
Signals
Table 234:
DPGGIO Input signals
Name
Type
OPEN
BOOLEAN
CLOSE
BOOLEAN
VALID
BOOLEAN
Table 235:
DPGGIO Output signals
Name
Type
POSITION
INTEGER
Settings
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).
Operation principle
Upon receiving the input signals, the IEC 61850 generic communication I/O functions
(DPGGIO) function block will send the signals over IEC 61850-8-1 to the equipment or
system that requests these signals. To be able to get the signals, PCM600 must be used to
define which function block in which equipment or system should receive this
information.
Default
Description
0
Open indication
0
Close indication
0
Valid indication
Description
Double point indication
1MRK 511 287-UUS A
Technical manual