1MRK 511 287-UUS A
7.4.3
7.4.4
7.4.5
Table 131:
LOVPTUV (27) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
VPG
1 - 100
tTrip
0.000 - 60.000
Technical manual
The operation of LOVPTUV (27) is supervised by the fuse failure supervision
SDDRFUF.
Function block
LOVPTUV (27)
V3P*
TRIP
BLOCK
PICKUP
CBOPEN
BLKV
ANSI09000279-1-en.vsd
ANSI09000279 V1 EN
Figure 76:
LOVPTUV (27) function block
Signals
Table 129:
LOVPTUV (27) Input signals
Name
Type
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
CBOPEN
BOOLEAN
BLKV
BOOLEAN
Table 130:
LOVPTUV (27) Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
Settings
Unit
Step
-
-
%VB
1
s
0.001
Default
Description
-
Three phase group signal for voltage inputs
0
Block of function
0
Circuit breaker open
0
Block from voltage circuit supervision
Description
Trip signal
Pickup signal
Default
Description
Disabled
Operation Enable/Disable
70
Operate voltage in% of base voltage Ubase
7.000
Operate time delay
Section 7
Voltage protection
187