Current protection
6.7.5
Table 68:
CCRBRF (50BF) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
FunctionMode
Current
Contact
Current&Contact
BuTripMode
2 out of 4
1 out of 3
1 out of 4
RetripMode
Retrip Off
CB Pos Check
No CBPos Check
Pickup_PH
5 - 200
Pickup_N
2 - 200
t1
0.000 - 60.000
t2
0.000 - 60.000
Table 69:
CCRBRF (50BF) Group settings (advanced)
Name
Values (Range)
Pickup_BlkCont
5 - 200
Table 70:
CCRBRF (50BF) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
138
Table 67:
CCRBRF (50BF) Output signals
Name
Type
TRBU
BOOLEAN
TRRET
BOOLEAN

Settings

Unit
Step
-
-
-
-
-
-
-
-
%IB
1
%IB
1
s
0.001
s
0.001
Unit
Step
%IB
1
Unit
Step
-
1
Description
Back-up trip by breaker failure protection function
Retrip by breaker failure protection function
Default
Description
Disabled
Disable/Enable Operation
Current
Detection principle for back-up trip
1 out of 3
Back-up trip mode
Retrip Off
Operation mode of re-trip logic
10
Phase current pickup in % of IBase
10
Operate residual current level in % of IBase
0.000
Time delay of re-trip
0.150
Time delay of back-up trip
Default
Description
20
Current for blocking of 52a operation in % of
Ibase
Default
Description
1
Selection of one of the Global Base Value
groups
1MRK 511 287-UUS A
Technical manual

Advertisement

Table of Contents
loading

Table of Contents