Functionality; Function Block; Signals - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

Section 6
Current protection
6.10.2
6.10.3
6.10.4
6.10.5
Table 87:
BRCPTOC (46) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
Pickup_ub
50 - 90
Pickup_PH
5 - 100
tOper
0.000 - 60.000
150

Functionality

Conventional protection functions can not detect the broken conductor condition. Broken
conductor check BRCPTOC (46) function, consisting of continuous phase selective
current unsymmetrical check on the line where the IED is connected will give alarm or trip
at detecting broken conductors.

Function block

BRCPTOC (46)
I3P*
TRIP
BLOCK
PICKUP
ANSI09000277-1-en.vsd
ANSI09000277 V1 EN
Figure 62:
BRCPTOC (46) function block

Signals

Table 85:
BRCPTOC (46) Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
Table 86:
BRCPTOC (46) Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
Settings
Unit
Step
-
-
%IM
1
%IB
1
s
0.001
Default
Description
-
Three phase group signal for current inputs
0
Block of function
Description
Operate signal of the protection logic
Pickup signal of the protection logic
Default
Description
Disabled
Operation Disable / Enable
50
Unbalance current operation value in percent
of max current
20
Minimum phase current for operation of
pickup_ub> in % of Ibase
5.000
Operate time delay
1MRK 511 287-UUS A
Technical manual

Advertisement

Table of Contents
loading

Table of Contents