Section 6
Current protection
6.2.3
6.2.4
86
Second harmonic blocking level can be set for the function and can be used to block each
step individually

Function block

OC4PTOC (51_67)
I3P*
TRIP
V3P*
TRST1
BLOCK
TRST2
BLK1
TRST3
BLK2
TRST4
BLK3
PICKUP
BLK4
PU_ST1
PU_ST2
PU_ST3
PU_ST4
PU_A
PU_B
PU_C
2NDHARM
ANSI08000002-2-en.vsd
ANSI08000002 V2 EN
Figure 30:
OC4PTOC (51/67) function block

Signals

Table 30:
OC4PTOC (51_67) Input signals
Name
Type
I3P
GROUP
SIGNAL
U3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKST1
BOOLEAN
BLKST2
BOOLEAN
BLKST3
BOOLEAN
BLKST4
BOOLEAN
Table 31:
OC4PTOC (51_67) Output signals
Name
Type
TRIP
BOOLEAN
TR1
BOOLEAN
TR2
BOOLEAN
TR3
BOOLEAN
Table continues on next page
Default
Description
-
Three phase group signal for current inputs
-
Three phase group signal for voltage inputs
0
Block of function
0
Block of step 1
0
Block of step 2
0
Block of step 3
0
Block of step 4
Description
Common trip signal
Trip signal from step 1
Trip signal from step 2
Trip signal from step 3
1MRK 511 287-UUS A
Technical manual