Section 12
Monitoring
Name
Values (Range)
tResetLevelLO
0.000 - 60.000
tResetTempLO
0.000 - 60.000
tResetTempAlm
0.000 - 60.000
12.17.6
12.17.7
12.18
12.18.1
524
Unit
Step
s
0.001
s
0.001
s
0.001

Operation principle

Insulation liquid monitoring function SSIML (71) is used to monitor oil level in the circuit
breaker. Two binary output signals are used from the circuit breaker to initiate alarm
signals, level below alarm level and level below lockout level. If the input signal
LVL_ALM is high, which indicate that the oil level in the circuit breaker is below alarm
level, the output signal LVL_ALM, level below alarm level, will be initiated after a set
time delay and indicate that maintenance of the circuit breaker is required. Similarly, if the
input signal LVL_LO is high, which indicate oil level in the circuit breaker is below
lockout level, the output signal LVL_LO, will be initiated after a time delay. The two time
delay settings, tLevelAlarm and tLevelLockOut, are included in order not to initiate any
alarm for short sudden changes in the oil level. If the oil level in the circuit breaker goes
below the levels for more than the set time delays the corresponding signals, LVL_ALM,
level below alarm level and LVL_LO, level below lockout level alarm will be obtained.
The input signal BLK_ALM is used to block the two alarms levels. The input signal
BLOCK is used to block both the alarms and the function.
Technical data
Table 426:
SSIML(71) Technical data
Function
Timers
Circuit breaker condition monitoring SSCBR
Identification
Function description
Circuit breaker condition monitoring
Default
Description
0.000
Reset time delay for level lockout
0.000
Reset time delay for temperture lockout
0.000
Reset time delay for temperture alarm
Range or value
(0.000-60.000) s
IEC 61850
IEC 60617
identification
identification
SSCBR
-
1MRK 511 287-UUS A
Accuracy
± 0.5% ± 110 ms
ANSI/IEEE C37.2
device number
-
Technical manual