ABB REC650 ANSI Technical Manual page 517

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

1MRK 511 287-UUS A
Technical manual
F
A
Z
pZ
I
A
L
A
V
A
ANSI01000171 V1 EN
Figure 225:
Fault on transmission line fed from both ends
From figure
225
it is evident that:
=
× ×
+ ×
V
I p Z
I R
A
A
L
F
F
EQUATION1595 V1 EN
Where:
I
is the line current after the fault, that is, pre-fault current plus current change due to the fault,
A
I
is the fault current and
F
is a relative distance to the fault
p
The fault current is expressed in measurable quantities by:
I
F A
------- -
I
=
F
D
A
EQUATION96 V1 EN
Where:
I
is the change in current at the point of measurement, IED A and
FA
D
is a fault current-distribution factor, that is, the ratio between the fault current at line end A and the
A
total fault current.
For a single line, the value is equal to:
L
B
(1-p).Z
I
L
B
I
F
R
F
xx01000171_ansi.vsd
Section 12
Monitoring
Z
B
(Equation 61)
(Equation 62)
511