1MRK 511 287-UUS A
12.15.9
12.16
12.16.1
12.16.2
12.16.3
Technical manual
Technical data
Table 418:
SPVNZBAT Technical data
Function
Lower limit for the battery terminal
voltage
Reset ratio, lower limit
Upper limit for the battery terminal
voltage
Reset ratio, upper limit
Timers
Battery rated voltage
Insulation gas monitoring function SSIMG (63)
Identification
Function description
Insulation gas monitoring function
Functionality
Insulation gas monitoring function SSIMG (63) is used for monitoring the circuit breaker
condition. Binary information based on the gas pressure in the circuit breaker is used as
input signals to the function. In addition, the function generates alarms based on received
information.
Function block
SSIMG (63)
BLOCK
PRESSURE
BLK_ALM
PRES_ALM
PRESSURE
PRES_LO
TEMP
TEMP
PRES_ALM
TEMP_ALM
PRES_LO
TEMP_LO
SET_P_LO
SET_T_LO
RESET_LO
ANSI09000129-1-en.vsd
ANSI09000129 V1 EN
Figure 228:
SSIMG (63) function block
Range or value
(60-140) % of Vbat
<105 %
(60-140) % of Vbat
>95 %
(0.000-60.000) s
20-250V
IEC 61850
IEC 60617
identification
identification
SSIMG
-
Section 12
Monitoring
Accuracy
± 1.0% of set battery voltage
-
± 1.0% of set battery voltage
-
± 0.5% ± 110 ms
-
ANSI/IEEE C37.2
device number
63
519