Settings - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

1MRK 511 287-UUS A
12.17.5
Table 425:
SSIML (71) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
LevelAlmLimit
0.00 - 25.00
LevelLOLimit
0.00 - 25.00
TempAlarmLimit
-40.00 - 200.00
TempLOLimit
-40.00 - 200.00
tLevelAlarm
0.000 - 60.000
tLevelLockOut
0.000 - 60.000
tTempAlarm
0.000 - 60.000
tTempLockOut
0.000 - 60.000
tResetLevelAlm
0.000 - 60.000
Table continues on next page
Technical manual
Table 423:
SSIML (71) Input signals
Name
Type
BLOCK
BOOLEAN
BLK_ALM
BOOLEAN
LEVEL
REAL
TEMP
REAL
LVL_ALM
BOOLEAN
LEVEL_LO
BOOLEAN
SET_L_LO
BOOLEAN
SET_T_LO
BOOLEAN
RESET_LO
BOOLEAN
Table 424:
SSIML (71) Output signals
Name
Type
LEVEL
REAL
LVL_ALM
BOOLEAN
LVL_LO
BOOLEAN
TEMP
REAL
TEMP_ALM
BOOLEAN
TEMP_LO
BOOLEAN

Settings

Unit
Step
-
-
-
0.01
-
0.01
-
0.01
-
0.01
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001
Default
Description
0
Block of function
0
Block all the alarms
0.0
Level input from CB
0.0
Temperature of the insulation medium from CB
0
Level alarm signal
0
Level lockout signal
0
Set level lockout
0
Set temperature lockout
0
Reset level and temperature lockout
Description
Level service value
Level below alarm level
Level below lockout level
Temperature of the insulation medium
Temperature above alarm level
Temperature above lockout level
Default
Description
Disabled
Disable/Enable Operation
5.00
Alarm setting for level
3.00
Level lockout setting
30.00
Temperature alarm level setting of the medium
30.00
Temperature lockout level of the medium
0.000
Time delay for level alarm
0.000
Time delay for level lockout indication
0.000
Time delay for temperature alarm
0.000
Time delay for temperture lockout
0.000
Reset time delay for level alarm
Section 12
Monitoring
523