Section 6
Current protection
6.4.5
Table 45:
EF4PTOC Group settings (basic)
Name
Values (Range)
Operation
Off
On
EnaDir
Disable
Enable
AngleRCA
-180 - 180
polMethod
Voltage
Current
Dual
UPolMin
1 - 100
IPolMin
2 - 100
RPol
0.50 - 1000.00
XPol
0.50 - 3000.00
I>Dir
1 - 100
2ndHarmStab
5 - 100
Table continues on next page
100
Table 44:
EF4PTOC Output signals
Name
Type
TRIP
BOOLEAN
TR1
BOOLEAN
TR2
BOOLEAN
TR3
BOOLEAN
TR4
BOOLEAN
START
BOOLEAN
ST1
BOOLEAN
ST2
BOOLEAN
ST3
BOOLEAN
ST4
BOOLEAN
STFW
BOOLEAN
STRV
BOOLEAN
2NDHARMD
BOOLEAN

Settings

Unit
Step
-
-
-
-
Deg
1
-
-
%UB
1
%IB
1
ohm
0.01
ohm
0.01
%IB
1
%
1
Description
General trip signal
Trip signal from step 1
Trip signal from step 2
Trip signal from step 3
Trip signal from step 4
General start signal
Start signal step 1
Start signal step 2
Start signal step 3
Start signal step 4
Forward directional start signal
Reverse directional start signal
2nd harmonic block signal
Default
Description
Off
Operation Off / On
Enable
Enabling the Directional calculation
65
Relay characteristic angle (RCA)
Voltage
Type of polarization
1
Minimum voltage level for polarization (UN or
U2) in % of UBase
5
Minimum current level for polarization (IN or I2)
in % of IBase
5.00
Real part of source Z to be used for current
polarisation
40.00
Imaginary part of source Z to be used for
current polarisation
10
Current level (IN or I2) for direction release in %
of IBase
20
Second harmonic restrain operation in % of IN
amplitude
1MRK 511 287-UUS A
Technical manual

Advertisement

Table of Contents
loading

Table of Contents