1MRK 511 287-UUS A
10.2.4
Technical manual

Signals

Table 171:
SMBRREC (79) Input signals
Name
Type
ON
BOOLEAN
OFF
BOOLEAN
BLKON
BOOLEAN
BLKOFF
BOOLEAN
RESET
BOOLEAN
INHIBIT
BOOLEAN
RI
BOOLEAN
TRSOTF
BOOLEAN
ZONESTEP
BOOLEAN
THOLHOLD
BOOLEAN
CBREADY
BOOLEAN
52a
BOOLEAN
SYNC
BOOLEAN
WAIT
BOOLEAN
RSTCOUNT
BOOLEAN
Table 172:
SMBRREC (79) Output signals
Name
Type
BLOCKED
BOOLEAN
SETON
BOOLEAN
READY
BOOLEAN
ACTIVE
BOOLEAN
SUCCL
BOOLEAN
UNSUCCL
BOOLEAN
INPROGR
BOOLEAN
3PT1
BOOLEAN
3PT2
BOOLEAN
3PT3
BOOLEAN
3PT4
BOOLEAN
3PT5
BOOLEAN
CLOSECMD
BOOLEAN
Table continues on next page
Default
Description
0
Enables AR when Operation = ExternalCtrl
0
Disables AR when Operation = ExternalCtrl
0
Sets AR in blocked state
0
Releases AR from blocked state
0
Resets AR to initial conditions
0
Interrupts and inhibits reclosing sequence
0
Reclosing sequence starts by a protection trip signal
0
Makes AR to continue to shots 2-5 at a trip from SOTF
0
Coordination between local AR and down stream
devices
0
Holds AR in wait state
0
CB must be ready for CO/OCO operation to allow start /
close
0
Status of the circuit breaker Closed/Open
0
Synchronizing check fulfilled for 3Ph closing attempts
0
Wait for master in Multi-breaker arrangements
0
Resets all counters
Description
Wait for master in Multi-breaker arrangements
AR operation is switched on
Indicates that AR is ready for a new sequence
Reclosing sequence in progress
Activated if CB closes during the time tUnsucCl
Reclosing unsuccessful, signal resets after the reclaim
time
Reclosing shot in progress, activated during open reset
Three-phase reclosing in progress, shot 1
Three-phase reclosing in progress, shot 2
Three-phase reclosing in progress, shot 3
Three-phase reclosing in progress, shot 4
Three-phase reclosing in progress, shot 5
Closing command for CB
Section 10
Control
239