Settings - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

Section 10
Control
10.4.5.6
10.4.6
10.4.6.1
10.4.6.2
290
Table 206:
A1A2_DC (3) Output signals
Name
Type
089OPREL
BOOLEAN
089OPITL
BOOLEAN
089CLREL
BOOLEAN
089CLITL
BOOLEAN
DCOPTR
BOOLEAN
DCCLTR
BOOLEAN
VPDCTR
BOOLEAN

Settings

The function does not have any settings available in Local HMI or Protection and Control
IED Manager (PCM600).
Interlocking for bus-coupler bay ABC_BC (3)
Identification
Function description
Interlocking for bus-coupler bay
Functionality
The interlocking for bus-coupler bay (ABC_BC, 3) function is used for a bus-coupler bay
connected to a double busbar arrangement according to figure 137. The function can also
be used for a single busbar arrangement with transfer busbar or double busbar
arrangement without transfer busbar.
Description
Opening of 089 is allowed
Opening of 089 is not allowed
Closing of 089 is allowed
Closing of 089 is not allowed
The bus section disconnector is in open position
The bus section disconnector is in closed position
Switch status of 089 is valid (open or closed)
IEC 61850
IEC 60617
identification
identification
ABC_BC
-
1MRK 511 287-UUS A
ANSI/IEEE C37.2
device number
3
Technical manual

Advertisement

Table of Contents
loading

Table of Contents