Section 13
Metering
13.2.6
13.2.7
558

Monitored data

Table 457:
ETPMMTR Monitored data
Name
Type
EAFACC
REAL
EARACC
REAL
ERFACC
REAL
ERRACC
REAL
MAXPAFD
REAL
MAXPARD
REAL
MAXPRFD
REAL
MAXPRRD
REAL
Operation principle
The instantaneous output values of active and reactive power from the Measurements
(CVMMXN) function block are used and integrated over a selected time tEnergy to
measure the integrated energy. The energy values (in MWh and MVarh) are available as
output signals and also as pulsed output which can be connected to a pulse counter.
Outputs are available for forward as well as reverse direction. The accumulated energy
values can be reset from the local HMI reset menu or with input signal RSTACC.
The maximum demand values for active and reactive power are calculated for the set time
interval tEnergy. The maximum values are updated every minute and stored in a register
available over communication and from outputs MAXPAFD, MAXPARD, MAXPRFD,
MAXPRRD for the active and reactive power forward and reverse direction until reset
with input signal RSTDMD or from the local HMI reset menu.
Values (Range)
Unit
-
MWh
-
MWh
-
MVArh
-
MVArh
-
MW
-
MW
-
MVAr
-
MVAr
1MRK 511 287-UUS A
Description
Accumulated forward active
energy value
Accumulated reverse active
energy value
Accumulated forward reactive
energy value
Accumulated reverse reactive
energy value
Maximum forward active
power demand value for set
interval
Maximum reverse active
power demand value for set
interval
Maximum forward reactive
power demand value for set
interval
Maximum reactive power
demand value in reverse
direction
Technical manual