ABB REC650 ANSI Technical Manual page 388

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

Section 11
Logic
11.3.1.10
382
Signals
Table 281:
AND Input signals
Name
Type
INPUT1
BOOLEAN
INPUT2
BOOLEAN
INPUT3
BOOLEAN
INPUT4
BOOLEAN
Table 282:
AND Output signals
Name
Type
OUT
BOOLEAN
NOUT
BOOLEAN
Settings
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).
Set-reset memory function block SRMEMORY
Identification
Function description
Set-reset memory function block
Functionality
The Set-Reset function SRMEMORY is a flip-flop with memory that can set or reset an
output from two inputs respectively. Each SRMEMORY function block has two outputs,
where one is inverted. The memory setting controls if the flip-flop after a power
interruption will return the state it had before or if it will be reset. For a Set-Reset flip-flop,
SET input has higher priority over RESET input.
Table 283:
Truth table for the Set-Reset (SRMEMORY) function block
SET
RESET
OUT
1
0
1
0
1
0
1
1
1
0
0
0
Default
Description
1
Input signal 1
1
Input signal 2
1
Input signal 3
1
Input signal 4
Description
Output signal
Inverted output signal
IEC 61850
IEC 60617
identification
identification
SRMEMORY
NOUT
0
1
0
1
1MRK 511 287-UUS A
ANSI/IEEE C37.2
device number
-
-
Technical manual