Section 10
Control
10.2.5
Table 173:
SMBRREC (79) Group settings (basic)
Name
Values (Range)
Operation
Disabled
External ctrl
Enabled
t1 3Ph
0.000 - 60.000
tReset
0.00 - 6000.00
tSync
0.00 - 6000.00
tTrip
0.000 - 60.000
tCBClosedMin
0.00 - 6000.00
tUnsucCl
0.00 - 6000.00
Priority
None
Low
High
tWaitForMaster
0.00 - 6000.00
Table 174:
SMBRREC (79) Group settings (advanced)
Name
Values (Range)
NoOfShots
1
2
3
4
5
StartByCBOpen
Disabled
Enabled
CBAuxContType
NormClosed
NormOpen
Table continues on next page
240
Name
Type
WFMASTER
BOOLEAN
COUNT3P1
INTEGER
COUNT3P2
INTEGER
COUNT3P3
INTEGER
COUNT3P4
INTEGER
COUNT3P5
INTEGER
COUNTAR
INTEGER

Settings

Unit
Step
-
-
s
0.001
s
0.01
s
0.01
s
0.001
s
0.01
s
0.01
-
-
s
0.01
Unit
Step
-
-
-
-
-
-
Description
Signal to Slave issued by Master for sequential
reclosing
Counting the number of three-phase reclosing shot 1
Counting the number of three-phase reclosing shot 2
Counting the number of three-phase reclosing shot 3
Counting the number of three-phase reclosing shot 4
Counting the number of three-phase reclosing shot 5
Counting total number of reclosing shots
Default
Description
External ctrl
Disable/ExternalCtrl/Enable
6.000
Open time for shot 1, delayed reclosing 3ph
60.00
Duration of the reset time
30.00
Maximum wait time for synchronism-check OK
0.200
Maximum trip pulse duration
5.00
Minimum time that CB must be closed before
new sequence allows
30.00
Wait time for CB before indicating
Unsuccessful/Successful
None
Priority selection between adjacent terminals
None/Low/High
60.00
Maximum wait time for release from Master
Default
Description
1
Maximum number of reclosing shots 1-5
Disabled
To be set ON if AR is to be started by CB open
position
NormOpen
Select CB auxilary contact type NC/NO for
CBPOS input
1MRK 511 287-UUS A
Technical manual