Section 12
Monitoring
Name
Values (Range)
IndicationMa15
Hide
Show
TrigLevel16
Trig on 0
Trig on 1
IndicationMa16
Hide
Show
12.4.6
480
Unit
Step
-
-
-
-
-
-

Operation principle

Disturbance report DRPRDRE is a common name for several functions to supply the
operator, analysis engineer, and so on, with sufficient information about events in the
system.
The functions included in the disturbance report are:
Sequential of events
Indications
Event recorder
Trip value recorder
Disturbance recorder
Figure 216
shows the relations between Disturbance Report, included functions and
function blocks. Sequential of events , Event recorder and Indications uses information
from the binary input function blocks (BxRBDR). Trip value recorder uses analog
information from the analog input function blocks (AxRADR). Disturbance recorder
DRPRDRE acquires information from both AxRADR and BxRBDR.
Default
Description
Hide
Indication mask for binary channel 15
Trig on 1
Trigger on positive (1) or negative (0) slope for
binary input 16
Hide
Indication mask for binary channel 16
1MRK 511 287-UUS A
Technical manual