ABB REC650 ANSI Technical Manual page 96

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

Section 6
Current protection
faultState
I3P
V3P
ANSI05000740 V2 EN
Figure 31:
Functional overview of OC4PTOC (51/67)
90
The direction element
The harmonic Restraint Blocking function
The four step over current function
The mode selection
If VT inputs are not available or not connected, setting parameter
DirModeSelx shall be left to default value, Non-directional.
dirPhAFlt
Direction
Element
dirPhBFlt
dirPhCFlt
Harmonic
harmRestrBlock
Restraint
Element
enableDir
Mode Selection
enableStep1-4
DirectionalMode1-4
The sampled analog phase currents are processed in a pre-processing function block.
Using a parameter setting MeasType within the general settings for the four step phase
overcurrent protection 3-phase output function OC4PTOC (51/67), it is possible to select
1MRK 511 287-UUS A
4 step over current
element
One element for each
step
ANSI05000740-2-en.vsd
Technical manual
faultState
PICKUP
TRIP

Advertisement

Table of Contents
loading

Table of Contents