Operation Principle - ABB REC650 ANSI Technical Manual

Relion 650 series bay control
Hide thumbs Also See for REC650 ANSI:
Table of Contents

Advertisement

1MRK 511 287-UUS A
14.4.5
14.5
14.5.1
14.5.2
Technical manual

Operation principle

The OUTxVAL output, where 1≤x≤16, will be HIGH if the incoming message is with
valid data.
The OUTxVAL output contains both quality validity and communication validity since
GOOSEBINRCV function has no COMMVALID output.
The input of this GOOSE block must be linked in SMT by means of a cross
to receive the binary values.
The implementation for IEC61850 quality data handling is restricted to a
simple level. If quality data validity is GOOD then the OUTxVAL output
will be HIGH. If quality data validity is INVALID, QUESTIONABLE,
OVERFLOW, FAILURE or OLD DATA then the OUTxVAL output will
be LOW.
GOOSE function block to receive a double point value
GOOSEDPRCV
Identification
Function description
GOOSE function block to receive a
double point value
Functionality
GOOSEDPRCV is used to receive a double point value using IEC61850 protocol via
GOOSE.
Station communication
IEC 61850
IEC 60617
identification
identification
GOOSEDPRCV
-
Section 14
ANSI/IEEE C37.2
device number
-
569

Advertisement

Table of Contents
loading

Table of Contents