1MRK 511 287-UUS A
Section 16
16.1
Technical manual
IED physical connections

Protective ground connections

The IED shall be grounded with a 6 Gauge flat copper cable.
The ground lead should be as short as possible, less than 59.06 inches
(1500 mm). Additional length is required for door mounting.
ANSI11000286 V2 EN
Figure 280:
The protective ground pin is located to the left of connector X101 on the
3U full 19" case